| Plan Review Notes For Permit 06110715 |
| Permit Number |
06110715 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-17 08:52:29 | DENIED BY BUILDING | | | | | | 1) THE STATE PRODUCT APPROVAL FOR THE ELITE INSULATED | | | ROOF PANELS HAS BEEN REVISED. PLEASE SUBMIT THE STATE | | | COVERSHEET FOR FL 5500-R1 AND THE INSTALLATION | | | INSTRUCTIONS THAT ARE LISTED ON THE STATE WEBSITE. ALSO | | | SUBMIT THE TEST DATA FROM THE WEBSITE FOR THE ROOF | | | PANELS THAT WILL BE INSTALLED ( CORE THICKNESS, FACING | | | THICKNESS AND CORE DENSITY MUST BE THE SAME AS PROPOSED | | | PRODUCT). | | | | | | 2) SPECIFY THE SKIN THICKNESS OF THE 3" PANEL ON THE | | | ENGINEERED DRAWINGS. | | | | | | 3) THE ENGINEERING IS FOR INSULATED PANELS WITH 2 LBS. | | | E.P.S. CORE MATERIAL. PROVIDE PRODUCT APPROVAL | | | INFORMATION FOR INSULATED PANELS WITH THE 2 LB CORE. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|