2006-12-09 14:33:56DENIED;
 RISER DIAGRAM DOES NOT MATCH FLOOR PLAN;
 1. ONLY ONE WATER CLOSET SHOWN ON FLOOR PLAN 2 SHOWN ON
 RISER DIAGRAM.
 2. ONLY ONE LAV, 2 SHOWN ON RISER DIAGRAM.
 3. NO SHOWER ON FLOOR PLAN BUT SHOWN ON RISER DIAGRAM.
 PLEASE REVISE RISER DIAGRAM TO MATCH FLOOR PLAN.
 JOHN LEECH
 805-6695