2006-12-06 14:01:47 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 2} RECEPTACLE SPACING 210.52(C) COUNTERTOPS. IN
 KITCHENS AND DINING ROOMS OF DWELLING UNITS, RECEPTACLE
 OUTLETS FOR COUNTER SPACES SHALL BE INSTALLED IN
 ACCORDANCE WITH 210.52(C)(1) THROUGH (5).
 (1) WALL COUNTER SPACES. A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH WALL COUNTER SPACE THAT IS 300 MM (12
 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS MORE THAN 600 MM
 (24 IN.) MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE.
  
 3} 210.8)A)(6) GFI REQUIRED, KITCHENS ? WHERE THE
 RECEPTACLES ARE INSTALLED TO SERVE THE COUNTERTOP
 SURFACES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  