| 2007-01-13 10:56:08 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS DESIGNED BY THE ARCHITECT. THE PERSONAL |
| | SIGNATURE OF THE ARCHITECT IS REQUIRED ON THE SEAL. IT |
| | APPEARS TO BE INITIALS WHICH IS NOT APPROVED. IF THIS |
| | IS INDEED THE LEGAL SIGNATURE OF THE ARCHITECT, A |
| | SIGNED, SEALED, NOTORIZED LETTER SHOWING THE LEGAL |
| | SIGNATURE OF THE ARCHITECT SHALL BE SUBMITTED FOR OUR |
| | FILES. -ALSO THE BUSINESS NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH |
| | SHEET. FAC 61G1-16.003, 61G1-16.004(2)(5) & FS 481.219, |
| | 481.2055. PLEASE MAKE SURE ALL REQUIREMENTS ARE |
| | ADDRESSED. |
| | |
| | 2. ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, |
| | ADDRESS, AND LICENSE NUMBER, AS WELL AS, THE NAME, |
| | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) |
| | & FS 471.025. PLEASE MAKE SURE ALL REQUIREMENTS ARE |
| | ADDRESSED.(SEE ATTACHED SHEET FROM DBPR WEBSITE). |
| | |
| | 3. SHTS P-1 & P-2 SANT RISER DIAGRAM. THE PUMP AT THE |
| | SANDWICH STATION REQUIRES A VENT CONNECTED TO THE VENT |
| | SYSTEM OR VENTED THRU THE ROOF. SECTION 916.5. (AAV NOT |
| | APPROVED). |
| | |
| | 4. SHT P-2 A FULL OPEN VALVE IS REQUIRED ON THE |
| | DISCHARGE SIDE OF THE CHECK VALVE FOR THE SUMP PUMP AT |
| | THE SANDWICH STATION. SECTION 712.2. PLEASE SHOW ON THE |
| | SANT. RISER DIAGRAM. |
| | |
| | 5. SHT P-2 WATER HAMMER ARRESTORS ARE REQUIRED ON ALL |
| | QUICK CLOSING VALVES. (SEE ICE MAKER). SECTION 604.9. |
| | |
| | REVIEW BY KEN STEVENS |