Plan Review Notes
Plan Review Notes For Permit 06110708
Permit Number 06110708
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-01-09 10:11:44*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF THE SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.WILL THE BUILDING OR PORTION OF THE BUILDING BE
 OCCUPIED DURING THE SCOPE OF WORK?IF SO, HOW WILL THE
 REQUIRED MEANS OF EGRESS BE MAINTAINED?
  
 4.WHAT IS THE OCCUPANT LOAD FOR THE BUILDING?
  
 5.ON SHEET A-1, ONE OF THE TWO FRONT ENTRY/EXIT DOORS
 SWINGS BACK INTO THE STORE.BE ADVISED THAT THE
 DOOR(S) WILL BE REQUIRED TO SWING IN THE DIRECTION OF
 EGRESS TRAVEL WHERE SERVING A ROOM OR AREA WITH AN
 OCCUPANT LOAD OF 50 OR MORE.
  
 6.AN ADDITIONAL DEVICE DIRECTING PERSONS TO THE REAR
 EXIT MAY BE NEEDED IF THE EXIT/EMERGENCY LIGHT ABOVE
 THE REAR DOOR IS NOT VISIBLE.
  
 7.INDICATE THE MINIMUM INTERIOR FINISH CLASSIFICATION
 FOR THE NEW CEILING TILES IN TERMS OF CLASS A, B, OR
 C.
  
 8.ON THE APPROPIATE PLAN SHEETS, RECTIFY THE
 DISCREPANCY OF THE DOOR SWING IN THE FOOD PREP AREA
 NEAR THE OVEN (FOR EXAMPLE SEE SHEET E-2 COMPARED TO
 F-1).THE REFERENCED DOOR SHOULD NOT OPEN INTO THE
 PATH OF THE REAR EXIT ACCESS CORRIDOR.
  
 9.PROVIDE DETAIL ON THE TYPES OF FOOD THAT WILL BE
 PREPARED ON THE ROLLER GRILLS AND PLEASE EXPLAIN "HOT
 SANDWICHES".
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW / WPBFR
 561-805-6722
  