Plan Review Notes
Plan Review Notes For Permit 06110708
Permit Number 06110708
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-08 18:07:33***UNSAT ***
  
  
 1) NOTE:PLEASE CORRELATE THE ADDRESS OF PROJECT.
 PLEASE SEE THE APPLIED ADDRESS FOR SITE IS INDICATED AS
 2995 45TH ST, ON PERMIT APPLICATION HOWEVER PLANS
 INDICATE 3225 CUMBERLAND DR.
  
 2) NOTE: PLEASE SHOW NEW OR EXISTING EXIT AND EMERGENCY
 LIGHTING PER NFPA-101 2003, 7.8, 7.9. PLEASE ALSO
 INDICATE CIRCUITING IF NEW ARE TO BE INSTALLED PER
 700.12E.
  
 3) NOTE:PLEASE INDICATE NEW OR EXISTING SIGN CIRCUIT
 PER 600.5, 220.3B6.
  
 4) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF ANY
 MATERIALS ARE OWNER SUPPLIED. THE VALUE AS APPLIED FOR
 IS EXTREMELY LOW FOR SCOPE OF WORK SHOWN. PLEASE KNOW
 IF AN APPROPRIATE VALUE IS NOT SUBMITTED ONE WILL BE
 ASSESSED USING THE FBC TABLES ALONG WITH THE MARSHALL?S
 AND SWIFT GUIDE AS ADOPTED INTO THE FBC.
 108.3.
  
 5) NOTE: PLEASE KNOW THE PLANS SUBMITTED ARE NOT
 COMPLETE FOR CODE COMPLIANCE. PLEASE SEE ONLY SOME CODE
 ARTICLES BELOW ARE BEING GIVEN. PLEASE KNOW THERE IS A
 SUBSTANTIALLY AMOUNT OF CODE RELATED ITEMS NOT
 SUBMITTED OR SHOWN.
  
 A) PLEASE INDICATE AND SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED.
 240.4,310.16, 408.4
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH. 106.1.2, 106.3.5.1.2 ETC.
 PLEASE ALSO SEE 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72, NFPA-30A ETC ETC.
 B) PLEASE SUBMIT LOAD CALCULATIONS.NEC 220. PLEASE
 SEE MDP SHOWN WITH NO LOAD?
 C) PLEASE SEE NEC 511 FOR VERIFICATION OF EXISTING SITE
 COMPLIANCE.
 D) PLEASE SEE LS 101 7.8, 7.9 FOR MISSING EM/ EXT LTS,
 PLEASE ALSO SEE 700.12E FOR CIRCUITING. AS NOTED
 ABOVE.
 E) PLEASE SEE 210.62, 210.12 FOR MISSING NEW OR
 EXISTING SHOW/DISPLAY WINDOWSRECEPTACLES REQUIRED.
 F) PLEASE SEE 250.110, 250.110
 G) PLEASE SEE 250.50
 H) PLEASE SEE 210.8B3
 I) PLEASE SEE FBC CHAPTER 13(ALL APPLICABLE SECTIONS,
 TOO MANY TO LIST AT THIS TIME.
 J) PLEASE SEE 110.9, 240.12 FOR MISSING AIC RATINGS FOR
 NEW SERVICE EQUIPMENT,SELECTIVE COORDINATION DETAILS
 TO BE SUBMITTED.
 ETC.
  
 6) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS
 HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY
 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES
 ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL
 REMODEL, ETC INSTALL A COMPLETE EMERGENCY BACK UP
 GENERATOR SYSTEM. THIS WILL SUBSTANTIALLY CHANGE THE
 PLANS SUBMITTED.
 PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER
 NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME
 MOVER ETC ETC.
 PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3
 ETC
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]