| Plan Review Notes For Permit 06110681 |
| Permit Number |
06110681 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-02-23 16:02:22 | *****UNSAT***** | | | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW OF 12/28/2006 STILL NEED TO BE ADDRESSED. ALL | | | OTHER COMMENTS WERE ADDRESSED. | | | | | | | | | | | | | | | 3.INDICATE THE FIRE RATING FOR THE EXISTING DOORS IN | | | THE 1 HOUR RATED WALL. | | | | | | 6.ILLUSTRATE REQUIRED GROUNDING AND BONDING FOR THE | | | BOOTH OR ADD TO NOTES THAT THE BOOTH WILL BE PROPERLY | | | GROUNDED AND BONDED. | | | | | | 7. PROVIDE PRODUCT APPROVAL RATING AND SIZE OF SAFETY | | | STORAGE CABINET. | | | | | | 9.THE FIRE SUPPRESSION SYSTEM FOR THE BOOTH WILL | | | REQUIRE SEPARATE PLANS AND PERMIT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|