| Plan Review Notes For Permit 06110681 |
| Permit Number |
06110681 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-04 17:51:01 | DENIED | | | REFERENCE FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. ACCORDING TO THE MSDS SHEETS, AN EYE WASH/EMERGENCY | | | SHOWER IS REQUIRED. SECTIONS 411 & 411.1. | | | | | | 2. SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE EYE | | | WASH/EMERGENCY SHOWER. THE EW/SHR SHALL BE LOCATED IN | | | CLOSE PROXIMITY TO THE HAZARD SOURCE. | | | | | | 3. SUBMIT A WATER RISER DIAGRAM SHOWING PIPE SIZE, | | | VALVES & POINT OF CONNECTION. SECTION | | | 106.3.5.1.3(3)(10)(13). | | | | | | 4. EYE WASH/EMERGENCY SHOWER APPROVAL REQUIRED. SUBMIT | | | MANUF. SPECIFICATION SHEETS. ISEA Z358.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|