Plan Review Notes
Plan Review Notes For Permit 06110680
Permit Number 06110680
Review Stop P
Sequence Number 3
Notes
Date Text
2007-02-02 14:59:51DENIED 3RD TIME
 REFERENCE: FBC-2004 BUILDING, SECTION 424.1
  
 THE FOLLOWING CORRECTION IS STILL REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE PERMIT BEING APPLIED FOR IS DEFINED IN THE
 FBC-2004 BUILDING SECTION 424.1 AS AN "INTERACTIVE
 WATER FEATURE" WHICH MEANS A STRUCTURE DESIGNED TO
 ALLOW FOR RECREATIONAL ACTIVITIES WITH RECIRCULATED,
 FILTERED, AND TREATED WATER, BUT HAVING MINIMAL
 STANDING WATER. WATER FROM THE INTERACTIVE FOUNTAIN
 TYPE FEATURES IS COLLECTED BY GRAVITY BELOW GRADE IN A
 COLLECTOR TANK OR SUMP. THE WATER IS FILTERED,
 DISINFECTED AND THEN PUMPED TO THE FEATURE DISCHARGE
 HEADS. THE SUBMITTED DRAWINGS INDICATE THE WATER BEING
 CONTINUOUSLY FED TO THE WATER FEATURES WITHOUT ANY
 TREATMENT AND IS A TREMENDOUS WASTE OF WATER. NOTE:
 YOUR RESPONSE LETTER STATES "THIS PLAYGROUND IS DEFINED
 AS A DRAIN-AWAY SYSTEM. THE WATER IS USED ONLY ONCE AND
 DISCHARGED." PLEASE GIVE A FBC-2004 CODE REFERENCE
 INDICATING THIS IS CODE COMPLIANT ON THE RESUBMITTAL. I
 COULD NOT FIND IT. AS FOR YOUR REFERENCE TO THIS SAME
 TYPE OF WATER PLAYGROUND BEING CONSTRUCTED AT GAINES,
 PHIPPS, AND SOUTH OLIVE PARK FOR THE CITY OF WEST PALM
 BEACH. THIS MAY BE FACT, BUT THAT WAS WORK FROM THE
 PAST AND POSSIBLE DIFFERENT CODES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721