| 2006-12-22 09:44:01 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING AND FBC-2004 BUILDING |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE PERMIT BEING APPLIED FOR IS DEFINED IN THE |
| | FBC-2004 BUILDING SECTION 424.1 AS AN "INTERACTIVE |
| | WATER FEATURE" MEANS A STRUCTURE DESIGNED TO ALLOW FOR |
| | RECREATIONAL ACTIVITIES WITH RECIRCULATED, FILTERED, |
| | AND TREATED WATER; BUT HAVING MINIMAL STANDING WATER. |
| | WATER FROM THE INTERACTIVE FOUNTAIN TYPE FEATURES IS |
| | COLLECTED BYGRAVITY BELOW GRADE IN A COLLECTOR TANK |
| | OR SUMP. THE WATER IS FILTERED, DISINFECTED AND THEN |
| | PUMPED TO THE FEATURE SPRAY DISCHARGE HEADS. THE |
| | SUBMITTED DRAWINGS DO NOT SHOW WATER BEING |
| | RECIRCULATED, FILTERED, AND TREATED. THE SUBMITTED |
| | DRAWINGS INDICATE THE WATER BEING CONTINUOUSLY FED TO |
| | THE WATER FEATURES WITHOUT ANY TREATMENT AND IS A |
| | TREMENDOUS WASTE OF WATER. PLEASE RESUBMIT INDICATING |
| | COMPLIANCE. |
| | |
| | 2. ON SHEETS C-3 AND C-5 THE 2 INCH DRAIN LINE MUST |
| | DRAIN INTO THE SANITARY SYSTEM NOT THE STORM SYSTEM DUE |
| | TO THE UNSANITARY ACCIDENTS RELATED TO CHILDREN. PLEASE |
| | CORRECT THIS ON THE RESUBMITTAL. |
| | |
| | 3. ON SHEET C-6 THE PROPOSED 2 INCH WATER SUPPLY TO |
| | THE CONTROLLER MUST INDICATE A REDUCED PRESSURE |
| | PRINCIBLE BACKFLOW PREVENTER PER FBC-2004 PLUMBING, |
| | SECTION 608.13.2. PLEASE ADD THIS ON THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |