| Plan Review Notes For Permit 06110667 |
| Permit Number |
06110667 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-03-08 13:39:37 | *** FAILED *** | | | 1) PLEASE SHOW ON PLANS THAT THE EXHAUST TERMINATION | | | COMPLIES WITH THE FOLLOWING. | | | | | | *** 2004 FBC/M 502.7.3.6 TERMINATION POINT. | | | THE TERMINATION POINT FOR EXHAUST DUCTS DISCHARGING TO | | | THE ATMOSPHERE SHALL BE LOCATED WITH THE FOLLOWING | | | MINIMUM DISTANCES. | | | 1.FOR DUCTS CONVEYING EXPLOSIVE OR FLAMMABLE | | | VAPORS, FUMES OR DUSTS: 30 FEET (9144 MM) FROM THE | | | PROPERTY LINE; 10 FEET (3048 MM) FROM OPENINGS INTO THE | | | BUILDING; 6 FEET (1829 MM) FROM EXTERIOR WALLS AND | | | ROOFS; 30 FEET (9144 MM) FROM COMBUSTIBLE WALLS AND | | | OPENINGS INTO THE BUILDING WHICH ARE IN THE DIRECTION | | | OF THE EXHAUST DISCHARGE; 10 FEET (3048 MM) ABOVE | | | ADJOINING GRADE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|