| 2007-03-04 13:35:16 | ** UNSAT 2ND REVIEW** |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTES WHICH REFERENCED TO |
| | NEC 516 FOR INFORMATION TO BE DETAINED AND PROVIDED ON |
| | PLANS; HOWEVER AT THIS TIME ONLY THE INFORMATION FOR |
| | THE EXISTING DISCONNECT WHICH WAS UNDER PREVIOUS |
| | PERMITTED PLANS IS BEING SHOWN. |
| | PLEASE SEE 516.3B1-B4 EXAMPLES IN THE NEC WHICH IS |
| | REQUIRED FOR THE SPECIFIC INSTALLATION SHOWING THE |
| | LOCATIONS, CLASS AND DIVISIONS ON PLANS. |
| | PLEASE SEE THE SUBMITTALS WHICH ARE FOR THE PAINT BOOTH |
| | DO NOT SHOW WHETHER OR NOT THE PANEL IS INSIDE OR |
| | OUTSIDE THE BOOTH? SHOWN ON WALL/ BUT NOT CLEAR FOR |
| | LOCATION. |
| | |
| | 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME AND DOES NOT APPLY. |
| | |
| | ** PLEASE SEE THESE LOCATIONS SHALL BE CLEAR FOR USE OF |
| | MIXING ROOM AND BOOTH. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |