Plan Review Notes
Plan Review Notes For Permit 06110667
Permit Number 06110667
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-01-29 11:15:13****UNSAT*****NEED ADDITIONAL INFO
  
  
  
 1.PLEASE INDICATE IF THIS A SINGLE TENANT ARRANGEMENT
 IN THE BUILDING.
  
 2.PROVIDE UL NUMBER AND WALL DETAIL FOR THE 1 HOUR
 RATED WALL.
  
 3.INDICATE THE FIRE RATING FOR THE EXISTING DOORS IN
 THE 1 HOUR RATED WALL.
  
 4.WHAT WILL BE THE DIRECTION OF THE PAINT SPRAY
 VAPORS UPON LEAVING THE PAINT DUCTS?
  
 5.PLEASE INDICATE THE SEPARATION DISTANCE BETWEEN THE
 INTAKE AND EXHAUST DUCTS.2004 FBC/M 502.7.3.6
  
 6.ILLUSTRATE REQUIRED GROUNDING AND BONDING FOR THE
 BOOTH OR ADD TO NOTES THAT THE BOOTH WILL BE PROPERLY
 GROUNDED AND BONDED.
  
 7. PROVIDE PRODUCT APPROVAL RATING AND SIZE OF SAFETY
 STORAGE CABINET.
  
 8.FIRE EXTINGUISHER(S) WITH A RATING OF AT LEAST
 2A:10BC SHALL BE CERTIFIED AND TAGGED.
  
 9.THE FIRE SUPPRESSION SYSTEM FOR THE BOOTH WILL
 REQUIRE SEPARATE PLANS AND PERMIT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-8056722


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved