| 2007-01-10 07:03:09 | BUILDING PLAN REVIEW |
| | PERMIT: 06110667 |
| | ADD: 422 SUNSET RD |
| | CONT: BURKHARDT CONSTRUCTION |
| | TEL: (561)718-2602 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | --- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) PLEASE SUBMIT PLANS FOR THE PREMANUFACTURED SPRAY |
| | BOOTH, & PAINT MIXING ROOM. |
| | 416.2 SPRAY ROOMS. |
| | SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS |
| | AND HORIZONTAL ASSEMBLIES OR |
| | BOTH WITH NOT LESS THAN A 1-HOUR FIRE-RESISTANCE |
| | RATING. |
| | |
| | 416.2.1 SURFACES. |
| | THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH |
| | AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE |
| | OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO |
| | FACILITATE WASHING AND CLEANING, AND SHALL BE SO |
| | DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM |
| | SHALL NOT BE USED. |
| | |
| | |
| | 416.3 SPRAYING SPACES. |
| | SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST |
| | SYSTEM TO PREVENT THE ACCUMULATION |
| | OF FLAMMABLE MIST OR VAPORS IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING CODE, MECHANICAL . |
| | WHERE SUCH SPACES ARE NOT SEPARATELY ENCLOSED, |
| | NONCOMBUSTIBLE SPRAY CURTAINS SHALL |
| | BE PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE |
| | VAPORS. |
| | |
| | PLEASE PROVIDE INFORMATION HOW THE EXHAUST DUCT AND |
| | ROOF VENT WILL STAY ATTACHED TO THE ROOF IN A 140MPH |
| | EVENT. |
| | NO PERMIT APPLICATION HAS BEEN FILED TO HOOK UP THE |
| | EXHAUST DUCT FOR THE SPRAY BOOTH NOR THE GAS FIRED |
| | HEATER FOR SPRAY BOOTH. |
| | |
| | 416.4 FIRE PROTECTION. |
| | AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE |
| | PROVIDED IN ALL SPRAY , DIP AND IMMERSING SPACES AND |
| | STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE |
| | WITH CHAPTER 9 .PLEASE PROVIDE ADITIONAL INFORMATION. |
| | AT THIS TIME THERE HAS BEEN NO PERMIT APPLICATION BEEN |
| | FILED FOR THE FIRE SUPRESSION SYSTEM THAT IS REQUIRED |
| | FOR THE SPRAY BOOTH. SHEET 3 OF 4 INDICATES UNIT TO BE |
| | DESIGNED TO: |
| | A) AUTOMATIC WATER SPRINKLERS |
| | B) DRY CHEMICAL |
| | C) HALON 1211/ 1301 |
| | PLEASE HIGHLIGHT WHICH SYSTEM IS TO BE USED, AND |
| | PROVIDE ADDITIONAL INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |