Plan Review Notes
Plan Review Notes For Permit 06110610
Permit Number 06110610
Review Stop E
Sequence Number 2
Notes
Date Text
2007-05-22 09:34:36 
 DENIED/INCOMPLETE INFORMATION
  
 1} CHANGE THE APPLICATION DESCRIPTION TO INCLUDE ALL
 ELECTRICAL WORK INTENDED UNDER THIS PERMIT. A PERMIT
 SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED UNDER SECTION
 553.80, FLORIDA STATUTES, HAVE BEEN PAID. 108.1 FBC.
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 3} AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN EVERY HABITABLE ROOM AND
 BATHROOM.210.70(A)(1), INDICATE COMPLIANCE FOR THE
 "FLORIDA ROOM" ON THE PLAN.
  
 4} ADD RECEPTACLES TO THE FLORIDA ROOM FOR SPACING
 REQUIREMENTS OF 210.52(A)(1).
  
 5}INDICATE IF THE PANEL IN THE "UTILITY AREA" IS NEW
 OR EXISTING. IF NEW UNDER THIS APPLICATION, SUBMIT A
 RISER DIAGRAM SHOWING HOW IT IS FED, OCP , CONDUIT AND
 CONDUCTOR SIZE AND TYPES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  