| 2007-01-22 13:13:20 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY |
| | ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF THE AREAS BEING |
| | DRAINED. SHOW 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS ADDED TO THE SF OF THE ROOF. PLEASE SHOW THE |
| | NEW AREA BEING ADDED TO THE ROOF WHERE THE LOWER ROOF |
| | WILL BE COVERED BY THE NEW ROOF. INDICATE THE SIZE OF |
| | THE EXISTING ROOF DRAINS AND THE PIPING SIZE OF THE |
| | RWL'S AND BLDG. STORM DRAIN PIPING. SECTIONS 1106 & |
| | 1107 WITH ALL SUBSECTIONS & TABLES. SECTION 106.1.1. |
| | |
| | 2. SHT A3 MORE INFORMATION IS REQUIRED. DETAILS 1 & 2 |
| | INDICATE THAT THE ROOF ELEVATION IS 13'2", BUT DETAIL 2 |
| | SHOWS ONE 6"X12" SCUPPER WHICH APPEARS TO BE BELOW THE |
| | ROOF ELEVATION. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 3. SHT A3.1 DETAIL 1 INDICATE THE ELEVATION OF THE |
| | EXISTING ROOF AND THE ELEVATION OF THE NEW ROOF. PLEASE |
| | PROVIDE A DETAIL SHOWING HOW THE NEW ROOF CONNECTS TO |
| | THE EXISTING ROOF WHICH IS INDICATED AS 13'2". |
| | |
| | 4. SUBMIT A DETAIL FOR THE EXISTING ROOF SHOWING ALL |
| | EXISTING PRIMARY AND SECONDARY ROOF DRAINS. |
| | |
| | 5. SHT A3.1 DETAILS 4 & 5 LOWER ROOF IS NOT INDICATED |
| | ON THE ELEVATION SECTIONS ON SHT A-3. PLEASE INDICATE |
| | WHERE THESE LOWER ROOFS ARE ON THE ELEVATIONS TO |
| | CLARIFY THE LOCATIONS. SECTION 106.1.1. |
| | |
| | REVIEW BY KEN STEVENS |