| 2007-01-19 16:56:45 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SHEET A2 SPECIFIES STRUCTURE IS TYPE VI UNPROTECTED |
| | CONSTRUCTION. THE 2004 FBC HAS CHANGED THIS TO |
| | CONSTRUCTION TYPE V-B.PLEASE REVISE. |
| | |
| | 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE AWNINGS. |
| | |
| | 4) ADDITIONAL PERMITS WILL BE REQUIRED FOR ELECTRICAL, |
| | PLUMBING, ETC. |
| | |
| | 5) ROOF SCUPPERS ARE REQUIRED. SPECIFY THE SIZES AND |
| | LOCATIONS. THE ADDITIONAL AREA OF THE NEW ROOF AND |
| | INCREASED PARAPET WALLS MUST BE CONSIDERED. 1503.4.2 |
| | SCUPPER . |
| | WHERE REQUIRED FOR ROOF DRAINAGE, A SCUPPER SHALL |
| | BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR |
| | PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY |
| | THE SLOPE AND THE CONTRIBUTING AREA OF THE ROOF. THE |
| | EXTERIOR FACING OR LINING OF ASCUPPER , IF |
| | METAL, SHALL BE THE SAME AS FLASHING MATERIAL REQUIRED |
| | BY SECTIONS 1503 THROUGH 1510 FOR THE PARTICULAR TYPE |
| | OF COVERING SPECIFIED FOR THE BUILDING. FOR OTHER TYPE |
| | MATERIALS, FOLLOW MANUFACTURER?S SPECIFICATIONS. |
| | 1503.4.3 |
| | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS |
| | NOT PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN |
| | WALLS OR PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR |
| | MORE THAN 4 INCHES (102 MM) ABOVE THE FINISHED ROOF |
| | COVERING AND SHALL BELOCATED AS CLOSE AS PRACTICAL |
| | TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND |
| | PARAPET SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | 6) 1503.6 PROTECTION AGAINST DECAY AND TERMITES. |
| | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| | A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 7)THE SECTION MARKER FOR 3 / A3.1 ON SHEET A2 IS |
| | INCORRECTLY INDICATED THROUGH THE THE WINDOW INSTEAD OF |
| | THE DOOR. |
| | |
| | 8) PLEASE INDICATE THE PROPERTY LINES IN RELATION TO |
| | THE STRUCTURE. 3202.3 ENCROACHMENTS 8 FEET OR MORE |
| | ABOVE GRADE. |
| | ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE |
| | SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4 . |
| | |
| | 3202.2.2 ARCHITECTURAL FEATURES. |
| | COLUMNS OR PILASTERS, INCLUDING BASES AND MOLDINGS |
| | SHALL NOT PROJECT MORE THAN 12 INCHES (305 MM). BELT |
| | COURSES, LINTELS, SILLS, ARCHITRAVES, PEDIMENTS AND |
| | SIMILAR ARCHITECTURAL FEATURES SHALL NOT PROJECT MORE |
| | THAN 4 INCHES (102 MM). |
| | |
| | 9)ON SHEET S3 THE ROOF SHEATHING FASTENER SPACING IS |
| | INCORRECT. FBC TABLE 2304.9.1 REQUIRES 6" OC AT ZONES 1 |
| | & 2AND 4" OC IN ZONE 3. |
| | |
| | 10)SUBMIT PRODUCT APPROVALS FOR THE FOOF COVERING AT |
| | THE NEW ROOF AREA. |
| | |
| | 11) THE WRONG FLORIDA PRODUCT APPROVAL COVER SHEET & |
| | FL# FOR THE 3000/L-3000 STOREFRONTS WAS SUBMITTED. THE |
| | CORRECT ONE IS FL6297. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |