2006-12-05 14:58:23DENIED;
 SANITARY RISER DIAGRAM;
 1.AUOMATIC CLOTHES WASHER NOT SHOWN ON SANITARY RISER
 DIAGRAM. BRANCH DRAIN TO BE 3" WITH A CLEANOUT AT 48"
 AFF. SECTION 406.3.
 2.LAUNDRY SINK TO DISCHARGE DOWN STREAM OF THE BATHROOM
 GROUP. SEC. 909.1.
 3.FIRST FLOOR SHOWER NOT VENTED. MASTER BATH CANNOT
 DISCHARGE INTO THE VENT FOR THE 1ST FLOOR SHOWER.
 MASTER BATH MUST DISCHARGE DOWN STREAM OF THE FIRST
 FLOOR BATHROOM GROUP.