| 2006-12-04 10:48:06 | *** DENIED *** |
| | 1) MECHANICAL PLANS DUCT LAY-OUT IS DIFFICULT TO READ, |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY. |
| | PER 2004 FBC 106.1.1. |
| | |
| | 2) THE ARCHITECT JEFFREY GAPSTUR NEEDS TO SEAL THE |
| | MECHANICAL PLANS AS HIS INFORMATION IS IN THE TITLE |
| | BLOOK, PERFAC 61G1-16.003. |
| | |
| | 3) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 4)PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR GAS |
| | FIREPLACE. |
| | |
| | 5) OPEN GAS GRILL IN COVERED PORCH WILL NEED AN |
| | APPROVED EXHAUST HOOD, PER FBC/M 505.3. |
| | |
| | 6) NEED TO SHOW AN A/C EQUIPMENT LISTING WITH ALL |
| | PERTINENT INFORMATION ON THE MECHANICAL PLANS. |
| | |
| | 7) NEED TO PROVIDE COMBUSTION AIR FOR GAS CLOTHES DRYER |
| | OR PROVIDE COMBUSTION AIR CALCULATIONS, PER 2004 FBC/R |
| | M1701.1. |
| | |
| | 8) MECHANICAL PLANS ARE SHOWING A GAS WATER HEATER, THE |
| | ELECTIRACL AND PLUMBING PLANS ARE SHOWING A ELECTRIC |
| | WATER HEATER, PLEASE CORRECT. |
| | |
| | 9) 10" RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS |
| | TO BE 18", SEE (A) AND (C) EXSEPT. |
| | BALANCED RETURN AIR MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |
| | |
| | |
| | |
| | . |