Plan Review Notes
Plan Review Notes For Permit 06110599
Permit Number 06110599
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-30 20:16:19*** UNSAT ***
  
  
 1) NOTE: PLEASE BE SURE TO SPECIFY THE FOLLOWING CODES
 ON THE PLANS.
 2002 NFPA-70 AND 2002 NFPA-72
  
 2) NOTE: PLEASE SEE DEFINITIONS IN NFPA-72 FOR SMOKE
 DEVICES. PLEASE KNOW IF THESE DEVICES ARE PART OF A LOW
 VOLTAGE ALARM SYSTEM THEN THE SD DESIGNATION FOR SMOKE
 DETECTORS IS OK, HOWEVER IF INDEED THESE ARE 120V
 DEVICES WHICH DETECT AND ACTUALLY HAVE AN ALARM, PLEASE
 INDICATE AS "SA". THIS WAS RECENTLY BROUGHT TO OUR
 ATTENTION FROM NFPA WHICH IS NOT THE SAME AS THE
 STANDARD WHICH HAS BEEN REQUESTED ON ALL PREVIOUS
 REVIEWS.
  
 3) NOTE: PLEASE NOTE DEVICE LOCATIONS AND INSTALLATIONS
 PER 11.5.1.1, AND 11.8.3, AS THESE DEVICES SHALL BE
 LOCATED WITHIN 12 INCHES ON A FLAT CEILING. PLEASE KNOW
 ANY CEILING WHICH CONTAINS A TRAY HIGHER THAN 12
 INCHES, THEN THE DEVICE MUST BE INSTALLED WITHIN THE
 12".
 PLEASE SEE MISSING SA/SD AT THE LOWER LEVEL OF DWELLING
 IN THE IMMEDIATE VICINITY LEADING TO THE FLOOR ABOVE.
 NFPA-72 11.8.3
  
 4) NOTE: PLEASE SUBMIT MANUFACTURE SPEC/CUT SHEETS FOR
 THE PROPOSED MTS.PLEASE SEE THIS UNIT SHALL BE
 SERVICE ENTRANCE RATED.
 PLEASE SEE REQUIREMENTS FOR SERVICE ENTRANCE RATED
 DEVICES.
 PLEASE SEE AS THE MTS IS NOT SHOWN, MAINS ARE NOT
 GROUPED AT THIS TIME. 230.72
 PLEASE SEE 230.76, 230.79, 230.70, 90.7, AND 110.3 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 5) NOTE: PLEASE SEE 250.6 AND 250.24B, WHICH DOES NOT
 PERMIT EQUIPMENT GROUNDING CONDUCTORS INSTALLED UNTIL
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE RISER AND ADJUST.
  
 6) NOTE: PLEASE SEE MISSING SERVICE ENTRANCE
 CONDUCTORS, THE NOTE SEEMS TO START TO LIST A CERTAIN
 SIZE MCM, BUT DOES NOT GIVE SIZE. PLEASE SEE 310.15B6
 FOR MINIMUM SIZES.
 240.4, 310.16
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER.
 422.31
  
 8) NOTE: PLEASE VERIFY THE SIZE OF THE OF THE WH HEAT.
 PLEASE SEE 4KW DOES NOT SEEM TO BE A COMMON SIZE.
 PLEASE KNOW IN EITHER CASE THE MAXIMUM OCP IS 150%,
 422.11E3, OR MIN IS 125%. 422.13.
  
 9) NOTE: PLEASE LIST ALL THE ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE.
 210.12
  
 10) NOTE: PLEASE SEE MISSING DEDICATED BATH ROOM
 CIRCUITS AS REQUIRED PER 210.52D, 210.11C3. PLEASE SEE
 THERE ARE SEVERAL CIRCUITS WHICH ARE SHOWN AS GFI, YET
 ARE THESE FOR THE BATH ROOMS?
 408.4, 310.16, ETC.
  
 11) NOTE: PLEASE SEE MISSING KITCHEN ISLAND RECEPTS PER
 210.52C2
  
 12) NOTE: PLEASE SEE MISSING KITCHEN COUNTER SPACE
 RECEPTS PER 210.52C1
  
 13) NOTE: PLEASE SEE 210.8A6, AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE SHALL BE SHOWN AS GFI/GFI
 PROTECTED.
  
 14) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 AS
 1500VA SHALL BE FIGURED FOR EACH OF THE SMALL APPLIANCE
 CIRCUITS, EVEN IF MORE THAN 2. THERE ARE TWO SHOWN
 WHICH ARE OK, HOWEVER AS THE NOTED IN NOTE #10, THERE
 ARE SEVERAL GFI CIRCUITS, YET NOT CLEAR WHAT THESE ARE
 FOR.
  
 15) NOTE: PLEASE SEE ONE REDLINED SET FOR LOCATIONS FOR
 MISSING RECEPTS REQUIRED FOR WALL SPACE PER 210.52.
  
 16) NOTE: PLEASE SEE MISSING AIC RATINGS FOR ALL
 SERVICE EQUIPMENT.
 PLEASE KNOW THIS INCLUDES THE PROPOSED MTS.
 110.9, 702.5
  
 17) NOTE: PLEASE KNOW THE ADDRESS WHICH IS NOW KNOWN,
 SHALL BE INDICATED ON THE TITLE BLOCK. PLEASE SEE THE
 ADDRESS OF 3808 NORTHSHORE.
 FBC 106.1.2, FAC 61G1-16.004
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-30 20:13:27ROUTED BACK TO ZONING AT REQUEST PER ZONING.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved