| Date |
Text |
| 2006-11-30 20:16:19 | *** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE TO SPECIFY THE FOLLOWING CODES |
| | ON THE PLANS. |
| | 2002 NFPA-70 AND 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE DEFINITIONS IN NFPA-72 FOR SMOKE |
| | DEVICES. PLEASE KNOW IF THESE DEVICES ARE PART OF A LOW |
| | VOLTAGE ALARM SYSTEM THEN THE SD DESIGNATION FOR SMOKE |
| | DETECTORS IS OK, HOWEVER IF INDEED THESE ARE 120V |
| | DEVICES WHICH DETECT AND ACTUALLY HAVE AN ALARM, PLEASE |
| | INDICATE AS "SA". THIS WAS RECENTLY BROUGHT TO OUR |
| | ATTENTION FROM NFPA WHICH IS NOT THE SAME AS THE |
| | STANDARD WHICH HAS BEEN REQUESTED ON ALL PREVIOUS |
| | REVIEWS. |
| | |
| | 3) NOTE: PLEASE NOTE DEVICE LOCATIONS AND INSTALLATIONS |
| | PER 11.5.1.1, AND 11.8.3, AS THESE DEVICES SHALL BE |
| | LOCATED WITHIN 12 INCHES ON A FLAT CEILING. PLEASE KNOW |
| | ANY CEILING WHICH CONTAINS A TRAY HIGHER THAN 12 |
| | INCHES, THEN THE DEVICE MUST BE INSTALLED WITHIN THE |
| | 12". |
| | PLEASE SEE MISSING SA/SD AT THE LOWER LEVEL OF DWELLING |
| | IN THE IMMEDIATE VICINITY LEADING TO THE FLOOR ABOVE. |
| | NFPA-72 11.8.3 |
| | |
| | 4) NOTE: PLEASE SUBMIT MANUFACTURE SPEC/CUT SHEETS FOR |
| | THE PROPOSED MTS.PLEASE SEE THIS UNIT SHALL BE |
| | SERVICE ENTRANCE RATED. |
| | PLEASE SEE REQUIREMENTS FOR SERVICE ENTRANCE RATED |
| | DEVICES. |
| | PLEASE SEE AS THE MTS IS NOT SHOWN, MAINS ARE NOT |
| | GROUPED AT THIS TIME. 230.72 |
| | PLEASE SEE 230.76, 230.79, 230.70, 90.7, AND 110.3 ETC |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 5) NOTE: PLEASE SEE 250.6 AND 250.24B, WHICH DOES NOT |
| | PERMIT EQUIPMENT GROUNDING CONDUCTORS INSTALLED UNTIL |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE RISER AND ADJUST. |
| | |
| | 6) NOTE: PLEASE SEE MISSING SERVICE ENTRANCE |
| | CONDUCTORS, THE NOTE SEEMS TO START TO LIST A CERTAIN |
| | SIZE MCM, BUT DOES NOT GIVE SIZE. PLEASE SEE 310.15B6 |
| | FOR MINIMUM SIZES. |
| | 240.4, 310.16 |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER |
| | HEATER. |
| | 422.31 |
| | |
| | 8) NOTE: PLEASE VERIFY THE SIZE OF THE OF THE WH HEAT. |
| | PLEASE SEE 4KW DOES NOT SEEM TO BE A COMMON SIZE. |
| | PLEASE KNOW IN EITHER CASE THE MAXIMUM OCP IS 150%, |
| | 422.11E3, OR MIN IS 125%. 422.13. |
| | |
| | 9) NOTE: PLEASE LIST ALL THE ARC FAULT PROTECTED |
| | CIRCUITS ON PANEL SCHEDULE. |
| | 210.12 |
| | |
| | 10) NOTE: PLEASE SEE MISSING DEDICATED BATH ROOM |
| | CIRCUITS AS REQUIRED PER 210.52D, 210.11C3. PLEASE SEE |
| | THERE ARE SEVERAL CIRCUITS WHICH ARE SHOWN AS GFI, YET |
| | ARE THESE FOR THE BATH ROOMS? |
| | 408.4, 310.16, ETC. |
| | |
| | 11) NOTE: PLEASE SEE MISSING KITCHEN ISLAND RECEPTS PER |
| | 210.52C2 |
| | |
| | 12) NOTE: PLEASE SEE MISSING KITCHEN COUNTER SPACE |
| | RECEPTS PER 210.52C1 |
| | |
| | 13) NOTE: PLEASE SEE 210.8A6, AS ALL RECEPTS SERVING |
| | KITCHEN COUNTER SPACE SHALL BE SHOWN AS GFI/GFI |
| | PROTECTED. |
| | |
| | 14) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 AS |
| | 1500VA SHALL BE FIGURED FOR EACH OF THE SMALL APPLIANCE |
| | CIRCUITS, EVEN IF MORE THAN 2. THERE ARE TWO SHOWN |
| | WHICH ARE OK, HOWEVER AS THE NOTED IN NOTE #10, THERE |
| | ARE SEVERAL GFI CIRCUITS, YET NOT CLEAR WHAT THESE ARE |
| | FOR. |
| | |
| | 15) NOTE: PLEASE SEE ONE REDLINED SET FOR LOCATIONS FOR |
| | MISSING RECEPTS REQUIRED FOR WALL SPACE PER 210.52. |
| | |
| | 16) NOTE: PLEASE SEE MISSING AIC RATINGS FOR ALL |
| | SERVICE EQUIPMENT. |
| | PLEASE KNOW THIS INCLUDES THE PROPOSED MTS. |
| | 110.9, 702.5 |
| | |
| | 17) NOTE: PLEASE KNOW THE ADDRESS WHICH IS NOW KNOWN, |
| | SHALL BE INDICATED ON THE TITLE BLOCK. PLEASE SEE THE |
| | ADDRESS OF 3808 NORTHSHORE. |
| | FBC 106.1.2, FAC 61G1-16.004 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-11-30 20:13:27 | ROUTED BACK TO ZONING AT REQUEST PER ZONING. |