2006-12-08 18:01:02BUILDING REVIEW CHECKLIST:
 1- PROVIDE NOTICE OF COMMENCEMENT AS REQUIRED BY SEC.
 713.13 FLORIDA STATUTES.
  
 2- PROVIDE COPY OF IMPACT FEES PAID RECEIPT.
  
 3- SHEET A-1: TOTAL AREA DOESN'T ADD UP. REVISE TOTAL
 AREA AS REQUIRED. BREAK DOWN BALCONY AREAS TO PROPERLY
 ACCESS RADON FEES. NEED SQUARE FOOTAGE OF BALCONY WITH
 ROOF OVER AND BALCONY WITHOUT ROOF OVER.
  
 4- PROVIDE SOIL TEST REPORT. R401.4 2004 FLORIDA
 RESIDENTIAL CODE.
  
 5- TRUSS PACKAGE WILL BE REQUIRED TO BE SUBMITTED TO
 THIS OFFICE PRIOR TO INSTALLATION. TRUSS PACKAGE TO BE
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD. SEE
 SEC. R802.10.1 2004 FL. RESIDENTIAL CODE AND PROVIDE
 ALL REQUIRED INFORMATION.
  
 6- PROVIDE PLANS/SPECS FOR LOT DRAINAGE AS REQUIRED BY
 SEC. R401.3 2004 FL. RESIDENTIAL CODE. PROVIDE POSITIVE
 DRAINAGE WITHOUT GOING TO NEIGHBOR'S PROPERTY.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) PRECAST LINTELS.
 B) WINDOW MULLIONS.
 C) ENTRY DOORS.
 D) SIDE GARAGE DOOR.
 E) ALL SIMPSON OR USP CONNECTORS SPECIFIED IN PLANS
 AND DETAILS.
  
 8- PROVIDE FIREPLACE SPECS AND UL LISTING AS REQUIRED
 BY SEC. R1002.1 AND R1002.4 2004 FL. RESIDENTIAL CODE.
  
 9- PROVIDE SPECIFICATIONS AND LISTING FOR BBQ GRILLTO
 BE INSTALLED IN THE REAR PORCH AS REQUIRED BY SEC.
 G2447 2004 FL. RESIDENTIAL CODE. SPECS TO SHOW THAT
 PRODUCTISDESIGNED FOR PORCH INSTALLATION.
  
 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 11- SPECIFY ON PLANS THE CHIMNEY TERMINATION AS
 REQUIRED BY SEC. G2427.5.3 2004 RESIDENTIAL CODE.
  
 12- PROVIDE MANUFACTURER SPECS AND LISTING FOR ROOFAT
 CHIMNEY TERMINATION AS REQUIRED BY SEC. R1002.2 2004
 FL. RESIDENTIAL CODE. REVISE ELEVATIONS TO MATCH
 MANUFACTURER'S SPECS.
  
 13- PROVIDE COMPLETE RAILING AND GUARDRAIL DETAILS
 SHOWING COMPLIANCE WITH SEC. R312 2004 FL. RESIDENTIAL
 CODE. THIS APPLIES TO INTERIOR RAILINGS AND BALCONY
 GUARDRAIL.
  
 14- PROVIDE COMPLETE ENGINEERED PACKAGE OF EPICORE
 FLOOR SYSTEM.PACKAGE TO BE REVIEWED AND APPROVED BY
 THE ENGINEEROF RECORD PRIOR TO SUBMITTAL. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 15- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING
 AS REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC
 2004. (NOTE SAYING INSTALLATION PER PRODUCT APPROVAL IS
 NOT ACCEPTABLE. DESIGNERNEEDS TO SPECIFY FASTENING TO
 DEMONSTRATE COMPLIANCE WITH WIND CRITERIA. PRODUCT
 APPROVAL IS TO DEMONSTRATE THAT THE PRODUCT MEETS THE
 DESIGN CRITERIA.
  
 16- REVISE ENERGY CALCULATIONS. PROVIDE:
 A) CORRECT ADDRESS.
 B) CORRECT BUILDER.
 C) CORRECT PERMITTING OFFICE.
 D) CORRECT JURISDICTION.
 E) OWNER/AGENT TO SIGN AND DATE AT BOTTOM OF FORM.
  
 17- SHEET SP-1:
 A) SITE PLAN SHOWSARROWS DIRECTING TOWARD FRONT
 AND BACK OF PROPERTY.IF THIS IS FOR DRAINAGE, THEN
 NEED TO REVISE. NEED TO PROVIDE POSITIVE DRAINAGE AND
 IT CAN'T GO TO NEIGHBOR'S PROPERTY.
  
 B) COMPLETE INFORMATION REGARDING SURVEY
 INFORMATION. SEE NOTE AT BOTTOM OF SHEET.
  
 18- SHEET A-5: NEED CRICKET BY CHIMNEY. SEC. R1001.17
 2004 FL. RESIDENTIAL CODE.
  
 19- THE WIDTH OF STAIRWAY LANDING SHALL NOT BE LESS
 THAN THE STAIRWAY SERVED.REVISE LANDING WIDTH AS
 REQUIRED. SEC. R311.5.4 2004 FL. RESIDENTIAL CODE.
  
 20- BUILDING SECTION B/A-6: CORRECT REFERENCE FOR
 EVERYTHING RELATED TO STAIRWAY IS R311, NOT SEC.
 1009.11 FBC. REVISE AS REQUIRED.
  
 21- BUILDING SECTION A/A-7: REVISE ELEVATION REFERENCE
 FOR FIRST FLOOR AND SECOND FLOOR.IT READS ROOF TRUSS
 BEARING AT 21'-0".
  
 22- SHEET S-4: FRONT ELEVATION ISMISSING THE
 CALCULATED DESIGN PRESSURES FOR OPENINGS AT LIVING ROOM
 AND FOYER. SEC. R301 2004 FL. RESIDENTIAL CODE.
  
 23- SHEET S-5:
 A) TRUSS TIE DOWN SCHEDULE: REVISE NOTE #6. SEE
 SIMPSON CATALOGUE FOR REQUIRED EMBEDMENT. OTHERWISE
 PROVIDE COMPLETE ENGINEERING ANALYSIS IF SPECIFICATIONS
 ARE DIFFERENT FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B) REVISE TYPICAL STEP FOOTING DETAIL TO COMPLY WITH
 SEC. R311.5.3.2 2004 FL. RESIDENTIAL CODE.
  
 C) ROOF WIND PRESSURE CHART LOCATED ON RIGHT HAND
 SIDE OF TRUSS TIE DOWN SCHEDULE IS FOR WALLS NOT FOR
 ROOFS. REVISE TITLE AS REQUIRED.
  
 D) DESIGN LOAD SCHEDULE: NEED ATTIC LIVE LOAD AS
 REQUIRED BY TALE R301.5 2004 FL. RESIDENTIAL CODE.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER