| Plan Review Notes For Permit 06110577 |
| Permit Number |
06110577 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-17 16:19:27 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | | | | 1.)OPENING 7 SPECIFIES ANCHOR SPACING OF 15IN TOP AND | | | BOTTOM.NOT COMPLIANT FOR 7.5FT SPAN. | | | | | | 2.)OPENING 12 SPECIFIES ANCHOR SPACING OF 10IN TOP | | | AND BOTTOM.C1, TOP CONNECTION, REQUIRES 6IN TOP | | | ANCHOR SPACING. | | | | | | 3.)I HAVE SPOT CHECKED THE ANCHORING.BOTH OPENINGS | | | WHICH I HAVE CHECKED SPECIFIED ANCHORING NOT COMPLIANT | | | WITH THE PRODUCT APPROVAL.PLEASE CHECK ALL OPENINGS | | | AND REVISE AS NECESSARY. | | | | | | 4.)THE ANCHORING CIRCLED ON THE PRODUCT APPROVAL IS | | | FOR -31.2PSF.SEE THE DESIGN PRESSURE CHART WHICH YOU | | | HAVE PROVIDED.SOME OPENINGS HAVE DESIGN PRESSURES | | | WHICH EXCEED -31.2PSF.THOSE OPENINGS REQUIRE | | | ANCHORING FROM THE -47.2 ROW. | | | | | | | | | |
|