| Date |
Text |
| 2006-12-07 08:51:04 | *** UNSAT *** |
| | |
| | 1) NOTE:PLEASE SEE LOADS FOR SHOW WINDOWS NEED TO BE |
| | CLARIFIED PER 220.12A. PLEASE SEE AS THE VA IS NOT |
| | SHOWN AND NO LOAD SUMMARY IS SHOWN, THE VA PER FOOT CAN |
| | NOT BE VERIFIED. |
| | 210.62 |
| | |
| | 2) NOTE: PLEASE VERIFY THE LOAD SHOWN FOR THE SIGN |
| | CIRCUIT(S). PLEASE SEE 600.5, WHICH REFERENCES TO |
| | 220.3B6 FOR THE MINIMUM VA TO USE TO FIGURE FOR SIGN |
| | CIRCUITS. PLEASE SEE THE LOAD OF 5A?S FOR EACH DOES NOT |
| | CORRELATE TO THE MINIMUM VA REQUIRED. |
| | PLEASE SEE NO LOAD SUMMARY IS SHOWN TO VERIFY THIS. |
| | |
| | 3) NOTE: PLEASE CORRELATE LOADS ON PANEL FOR KNOWN |
| | RECEPTS ON A CIRCUIT. 220.13 |
| | |
| | 4) NOTE: PLEASE SEE A NOTE ON "E" UNIT INDICATES |
| | RECEPTACLE ABOVE CEILING AS TYPICAL FOR EACH SIGN |
| | CIRCUIT. PLEASE SEE 600.5, AS IT ONLY REQUIRES A |
| | CIRCUIT. PLEASE SEE 400.8(2) WHICH DO NOT PERMIT |
| | RECEPTACLES ABOVE CEILINGS AS THIS WOULD THEN CREATE |
| | THE ISSUE OF CORDS BEING RUN THROUGH CEILINGS WHICH IS |
| | NOT PERMITTED. |
| | PLEASE REVISE. |
| | |
| | 5) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE SYSTEM |
| | AS SHOWN. RISER SHOWS THE MAIN GROUNDING ELECTRODE |
| | BEING "TAPPED" AND SHOWN TO EACH MAIN DISCONNECT?? |
| | PLEASE SEE 250.24B, 250.6. PLEASE KNOW WHEN INSTALLING |
| | THE GUTTER, THE NEUTRAL CONDUCTOR WOULD BE "BONDED" TO |
| | THE GUTTER WHICH MAY CONTAIN THE SOLE CONNECTION OF THE |
| | GEC. PLEASE SEE ONLY ONE SET OF PHASE AND NEUTRAL |
| | CONDUCTORS WOULD THEN BE ROUTED TO EACH METER AND MAIN. |
| | EACH NEUTRAL WOULD BE BONDED TO THE ENCLOSURE AT THE |
| | FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE AS SHOWN THIS SEEM TO BE AN INTERESTING |
| | SCENARIO AT THE CONNECTION POINT SHOWN AT THE GROUND |
| | LEVEL LOCATION. |
| | ** PLEASE SEE THIS BEING AN EXISTING BUILDING AND THE |
| | CONCRETE ENCASED ELECTRODE ON AN EXISTING BUILDING IS |
| | NOT REQUIRED TO BE ATTACHED. PLEASE KNOW IF SHOWN ON |
| | GROUNDING ELECTRODE DETAIL BEING REQUIRED THEN THIS |
| | WILL BE REQUIRED IN THE FIELD. PLEASE VERIFY THIS BEING |
| | REQUIRED AND POSSIBLY AFFECTING THE STRUCTURAL |
| | INTEGRITY OF THE EXISTING FOOTER. |
| | |
| | 6) NOTE: PLEASE LIST THE FOLLOWING RELEVANT CODES ON |
| | THE PLANS. 2002 NFPA-70, 2003 NFPA-101 |
| | |
| | 7) NOTE: PLEASE CORRELATE LOADS, OVER CURRENT |
| | PROTECTION, CONDUCTORS ETC FOR THE A/C SYSTEMS. PLEASE |
| | SEE ELECTRICAL PLANS SEEM TO INDICATE A POSSIBLE 5KW |
| | LOAD, HOWEVER AS KW RATINGS/ KVA LOADS ARE NOT SHOWN, |
| | THESE ARE UNCLEAR AT THIS TIME. PLEASE SEE MECHANICAL |
| | PLANS CALL FOR 8KW AND 10KW UNITS. |
| | PLEASE SEE 424.3B, 310.16, 240.4 ETC |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |