| 2007-03-15 16:21:53 | *** DENIED *** |
| | 1) AS NOTED IN LAST REVIEW 11-21-06 NOTE #2. SEE |
| | COOLING LOAD CALCULATIONS SHOW THAT ALL FIVE BAYS |
| | TOGETHER WILL NEED OVER 460 TONS OF A/C, PLEASE SUBMIT |
| | CORRECTED COOLING LOAD CALCULATIONS, PER 2004 FBC |
| | 13-407.1.ABC.1. |
| | |
| | 2) THE ENGINEER EDWARD J. KRANZ WILL NEED TO SEAL THE |
| | MECHANICAL PLANS AS HIS INFORMATION IS IN THE TITLE |
| | BLOCK, SEE FAC 61G15-23.002. (SEE PLANS, PAGES M-1 AND |
| | M-2). |
| | |
| | 3) SEE PLANS, PAGE M-1 "O/A INTAKE" IF THIS IS TYPICAL |
| | OF 5 PLEASE STATE SO ON PLANS IF NOT GIVE INFORMATION |
| | AT EACH INTAKE. |
| | |
| | 4) SEE PLANS, PAGE M-1 " 6 INCH DUCT TO EXHAUST WALL |
| | LOUVER" IF TYPICAL OF 5 STATE SO ON PLANS IF NOT GIVE |
| | INFORMATION AT EACH EXHAUST. |
| | |
| | 5) SEE PLANS, PAGE 4 ELECTRICAL PLANS SHOW 7 A/C |
| | CONDENSER UNITS, MECHANICAL PLANS ONLY SHOW 5, PLEASE |
| | CORRECT ELECT. PLANS. |
| | |
| | 6) SEE PLANS, PAGE M-2A/C SCHEDULE SHOWS THE WRONG |
| | EQUIPMENT MANUFACTURE, CAPACITY (TOTAL) BTU'S, SENSIBLE |
| | BTU'S, AND A INCORRECT MODEL NUMBER FOR AHU #1. PLEASE |
| | REVIEW SUBMITTED MANUFACTURER'S SPECIFICATION'S FOR THE |
| | GOODMAN A/C AND CORRECT. |
| | |
| | 7) SEE ELECTRICAL REVIEW NOTE #2 AND 3. AS A RESULT OF |
| | DOCUMENTS BEING RETAINED PLEASE BE CERTAIN TWO COPY'S |
| | OF ALL INFORMATION IS BEING SUBMITTED. |
| | |
| | 8)SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR |
| | TIMES THE FEE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |