| 2007-03-10 18:17:38 | ** UNSAT 2ND REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE CORRELATE ELECTRICAL LIGHTING PLANS |
| | WITH THE ENERGY CALCULATIONS SUBMITTED. PLEASE SEE THE |
| | NUMBER OF FIXTURES; THE WATTAGE PER FIXTURE AND THE |
| | TOTAL DO NOT CORRELATE WITH THAT OF THE FIXTURES AND |
| | LIGHTING ON PLANS. |
| | PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE AN |
| | EXTERIOR LIGHTING, YET THE PLANS INDICATE EXTERIOR |
| | LIGHTING. |
| | 13-415.1.AB.1.1 |
| | 13-415.2 |
| | |
| | 2) NOTE: PLEASE SEE FBC 103.1, 103.1.1.1 AS THE ENERGY |
| | CALCULATIONS MUST BE SIGNED, DATED AND SEALED BY THE |
| | DESIGN PROFESSIONAL EVEN WHEN/IF FALLING UNDER THE |
| | EXCEPTIONS THAT A MECHANICAL CONTRACTOR PERFORMS THE |
| | SCOPE OF WORK. |
| | PLEASE KNOW THE SCOPE DOES NOT APPEAR TO FALL UNDER THE |
| | EXCEPTIONS UNDER FS 471.003. |
| | ** PLEASE ALSO SEE THE MECHANICAL PLANS WHICH CONTAIN |
| | TITLE BLOCKS FROM AN ENGINEER AND ENGINEERING FIRM, YET |
| | THERE IS A SIGNATURE AND SEAL ON THESE SHEETS FROM A |
| | MECHANICAL CONTRACTOR. THIS IS NOT PERMITTED UNDER |
| | FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.002 |
| | PLEASE ALSO SEE THE 2ND MECHANICAL SHEET IN EACH SET |
| | DOES NOT CONTAIN ANY SIGNATURE, DATE OR SEAL FROM |
| | ANYONE. |
| | |
| | 3) NOTE: PLEASE KNOW DUE TO THE COMMENTS ONE SET OF |
| | PLANS AND ENERGY CALCULATIONS WILL BE RETAINED BY THIS |
| | OFFICE. |
| | **PLEASE BE SURE RE-PRINT THE 2ND SET OF ELECTRICAL. AS |
| | PLUMBING IS ON THE SAME SHEET WITH ELECTRICAL, PLUMBING |
| | WILL NEED TO RE-STAMP SHEETS IN SETS WHEN PLANS ARE |
| | CORRECTED AND RESUBMITTED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |