| 2006-12-12 16:13:33 | *****DENIED***** |
| | |
| | |
| | |
| | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| | |
| | 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS |
| | SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE |
| | REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE |
| | FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 5.GASOLINE POWERED EQUIPMENT FOR DEMOLITION |
| | ACTIVITIES SHALL NOT BE USED TO PREVENTTHE |
| | POSSIBILITY OF CARBON DIOXIDE POISONING. |
| | |
| | 6.SHOW/DISPLAY THE ADDRESS OF THE STRUCTURE ON THE |
| | EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE HIGHWAY. AS |
| | PER WEST PALM BEACH CODE, THE NUMERICAL ADDRESS SHALL |
| | BE NO LESS THAN 6' IN HEIGHT AND 1" IN WIDTH. |
| | ADDITIONALLY, DISPLAY THE UNIT NUMBER (3" IN HEIGHT AND |
| | 1" IN WIDTH) FOR THE FRONT ENTRANCE TO DISTINGUISH ONE |
| | UNIT FROM THE OTHER. FRONT UNIT NUMBERS SHALL NOT BE ON |
| | THE DOORS OR WINDOWS, HOWEVER REAR UNIT NUMBER CAN BE |
| | INSTALLED ON THE DOOR.HURRICANE SHUTTERS SHALL NOT |
| | BLOCK VISIBILITY OF BUILDING AND/OR UNIT ADDRESS. |
| | |
| | 7.INTERIOR FINISH CLASSIFICATION IN AN UNSPRINKLERED |
| | BUILDING SHALL BE "A" OR "B". |
| | |
| | 8.FIRE EXTINGUISHERS TO BE 2A:10BC RATED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | CAPT. MICHEAL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |