| 2006-12-21 11:42:51 | BUILDING PLAN REVIEW |
| | PERMIT: 06110557 |
| | ADD: 2814 S. DIXIE HWY. |
| | CONT: KARNS CONSTRUCTION CORP. |
| | TEL: (561)805-7528 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW1ST. |
| | ACTION: DENIED |
| | |
| | NOTE: ANY OTHER OCCUPANCY OTHER THAN WHAT IS STATED BY |
| | THE DESIGNER OF RECORD SHALL REQUIRE A SEPERATE |
| | PERMIT. |
| | |
| | 1) 106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA. RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. SUBMIT PRODUCT APPROVALS FOR |
| | THE IMPACT WINDOWS/DOORS/ROOF AND STOREFRONT. |
| | |
| | 2)W.P.B. AMENDMENTS 108.3*IF IN THE OPINION OF THE |
| | BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING,ALTERATION APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL,ELECTRIC,PLUMBING,MECHANICAL,INTERIOR |
| | FINISH,ARCHITECTURAL AND DESIGN FEES,MARKETING COSTS, |
| | AND OVERHEAD AND PROFIT. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS |
| | SERVICES. |
| | |
| | 3)SHEET #1. IN REFERENCE TO THE DUMPSTER PAD, SEE |
| | REQUIREMENTS DETAILS IN PACKAGE AND COMPLY |
| | ACCORDINGLY. |
| | |
| | 4) FBC 11-4.3 SHOW THE ACCESSIBLE ROUTE TO THE BUILDING |
| | COMPLYING WITH THIS SECTION. |
| | |
| | 5)SHEET #2. THE CODE SECTION ON THE DRAWINGS IN |
| | REFERENCE TO ROOF DOWNSPOUTS IS FROM THE 2001 FBC. SEE |
| | FBC 2004 FOR CORRECT REFERENCE. |
| | |
| | 6)FBC 1503.4 UNLESS ROOF ARE SLOPED TO DRAIN OVER |
| | ROOF EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE |
| | SYSTEMS SHALL COMPLY WITH THE FBC PLUMBING CH. 11. |
| | |
| | 7)1503.4.3 |
| | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |