| 2007-11-29 12:18:26 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) NEED WIND LOAD CALCULATIONS TO SHOW THAT CONDENSER |
| | STANDS WILL WITHSTAND 140 MPH WINDS PER 2004 FBC 1609. |
| | IF PER-ENGINEERED CONDENSER STANDS SUBMIT PRODUCT |
| | APPROVAL OR AN NOA FOR PER-ENGINEERED CONDENSER STANDS, |
| | SEE FS 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND |
| | FAC 9B-72.010(31)(G). |
| | |
| | 2) PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO BEING |
| | SUBMITTED FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW |
| | STAMP AND SIGNATURE WILL MEET REQUIREMENT). SEE WPB |
| | AMEND. 106.3. |
| | |
| | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | |