Plan Review Notes
Plan Review Notes For Permit 06110556
Permit Number 06110556
Review Stop M
Sequence Number 8
Notes
Date Text
2007-11-29 12:18:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED WIND LOAD CALCULATIONS TO SHOW THAT CONDENSER
 STANDS WILL WITHSTAND 140 MPH WINDS PER 2004 FBC 1609.
 IF PER-ENGINEERED CONDENSER STANDS SUBMIT PRODUCT
 APPROVAL OR AN NOA FOR PER-ENGINEERED CONDENSER STANDS,
 SEE FS 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND
 FAC 9B-72.010(31)(G).
  
 2) PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO BEING
 SUBMITTED FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW
 STAMP AND SIGNATURE WILL MEET REQUIREMENT). SEE WPB
 AMEND. 106.3.
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]