Plan Review Notes
Plan Review Notes For Permit 06110556
Permit Number 06110556
Review Stop E
Sequence Number 6
Notes
Date Text
2007-07-06 18:21:452007-07-06 18:21:45
 NOTE ADDED:
  
 *** PLEASE KNOW , NO FURTHER ELECTRICAL REVIEWS OF
 ENERGY CALCULATIONS WILL BE DONE UNTIL A MEETING IS
 HELD WITH THE DESIGNERS OF RECORD. THESE NOTES WILL
 NEED TO BE GONE OVER AT THAT TIME TO ALLEAVIATE ANY
 QUESTIONS, COMMENTS OR CONFUSION OF ANYKIND.
2007-07-06 16:43:502007-07-06 18:21:45
 NOTE ADDED:
  
 *** PLEASE KNOW , NO FURTHER ELECTRICAL REVIEWS OF
 ENERGY CALCULATIONS WILL BE DONE UNTIL A MEETING IS
 HELD WITH THE DESIGNERS OF RECORD. THESE NOTES WILL
 NEED TO BE GONE OVER AT THAT TIME TO ALLEVIATE ANY
 QUESTIONS, COMMENTS OR CONFUSION OF ANYKIND.
 THIS WAS CONFIRMED WITH THE ASSISTANT BUILDING OFFICIAL
 AFTER REVIEW OF SAID ENERGY CALCULATIONS.
  
  
  
  
  
 2007-07-06 16:43:50
 ** UNSAT 6TH REVIEW **
  
  
 1) NOTE: PLEASE SEE NOTES DATED 6/29/07 WHICH STATED
 THIS OFFICE WAS GOING TO PLACE REVIEW INTO A *TEMPORARY
 FAILED STATUS*. THIS WAS TO ALLOW REVISED CORRECTED
 ENERGY CALCULATIONS TO BE BROUGHT IN AS A SUBMITTAL
 UNDER THE CORRECT VERSION AS LONG AS NO CHANGES WERE
 MADE TO THE CALCULATIONS THEMSELVES.
 ON TUESDAY JULY 3RD 2007 REVISED ENERGY CALCULATIONS
 WERE BROUGHT IN AS A SUBMITTAL TO THIS OFFICE. UPON A
 QUICK GLANCE TO THE CALCULATIONS IT WAS NOTICED THE
 VERSION WAS NOW STATED UNDER JULY 05 2.0 VERSION WHICH
 WAS BEFORE THE PREVIOUS CODE CHANGE. (PLEASE SEE THE
 FBC CHANGED AS OF OCT 1ST, 2005 OF THAT YEAR). THIS
 REVIEWER PLACED CALL TO THE ARCHITECT OF RECORD
 NOTIFYING OF THE INCORRECT VERSION. WE THEN CALLED THE
 PERSON WHICH WAS PROVIDING THE CALCULATIONS.
 THIS OFFICE SPECIFICALLY INFORMED BOTH DESIGNERS THAT
 THE ENERGY CALCULATIONS NUMBERS WERE OK, HOWEVER NEEDED
 TO BE UNDER THE 2.1 VERSION AS PREVIOUSLY STATED IN THE
 REVIEWS.
 THIS OFFICE WAS INFORMED THAT REVISED ENERGY
 CALCULATIONS WITH THE CORRECT VERSION WOULD BE
 SUBMITTED BY 7/06/07.
 PLEASE SEE NEW ENERGY CALCULATIONS WERE ONCE AGAIN
 BROUGHT IN BY THE PERMIT EXPEDITOR AS A SUBMITTAL AND
 NO FEE WAS CHARGED ON 7/06/07.
 PLEASE SEE THIS TIME THE VERSION WAS CORRECT HOWEVER
 THE NUMBERS IN THE ENERGY CALCULATIONS WHICH WERE OK ON
 THE PREVIOUS CALCULATIONS HAVE ONCE AGAIN BEEN CHANGED
 AND DO NOT MATCH AND CORRELATE WITH PLANS.
 PLEASE SEE 13-415.1.A, 13-415.2
  
 ** THIS REVIEW IS DENIED, ONE COPY OF EACH THE
 SUBMITTED ENERGY CALCULATIONS ARE BEING RETAINED BY
 THIS OFFICE.
  
 AS STATED ON PREVIOUS REVIEWS: PLEASE CORRELATE THE
 ENERGY CALCULATIONS WITH THE PLANS. PLEASE TAKE THE
 CALCULATIONS FOR ELECTRICAL LIGHTING FROM THE VERSION
 3.0 WHICH WAS SUBMITTED AND TRANSFER THAT INFORMATION
 INTO THE CORRECT VERSION OF 2.1.
 THE NUMBER OF LUMINARIES, THE WATTAGE OF LUMINARIES
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]