| 2007-06-10 11:57:32 | ** UNSAT 4TH REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED ARE |
| | SIGNED BY THE ARCHITECT, HOWEVER WAS INADVERTENTLY NOT |
| | SEALED AS NEEDED. |
| | PLEASE SEE ONLY ONE INPUT DATA REPORT WAS SUBMITTED. |
| | PLEASE SEE THE TOTAL AMOUNT OF FIXTURES, TYPES, AND |
| | WATTAGES DOES NOT MATCH PLANS. |
| | PLEASE SEE UNIT E FOR EXAMPLE> |
| | PLANS INDICATE RETAIL AS A TOTAL OF 11 FIXTURES, YET |
| | PLANS DO NOT INDICATE THE SAME AMOUNT OF FIXTURES ON |
| | THE PLANS. |
| | PLEASE SEE FIXTURE A, A TOTAL OF 7 OF THESE ARE ON |
| | PLANS, EACH OF THESE PER FIXTURE LEGEND IS 128WATTS. |
| | PLANS INDICATE A TOTAL OF 2-TYPE C WHICH ARE 32 WATTS |
| | EACH ON FIXTURE LEGEND. |
| | PLEASE SEE OFFICE AREA AS THE PLANS CALL FOR THIS |
| | FIXTURE AS 2-TYPE B EACH CONTAINING 3-32WATT BULBS AT A |
| | TOTAL OF 96WATTS, YET THE CALCULATIONS SHOWS 64WATTS. |
| | PLEASE SEE THE FIXTURE SCHEDULE WHICH CONTAINS FIXTURES |
| | WITH A DIFFERENT WATTAGE FOR THE SAME FIXTURES AS NOTED |
| | ON CALCULATIONS. |
| | UNIT ?E. |
| | 7- A FIXTURES 128W EACH |
| | 2-C FIXTURES 26 W EACH |
| | 2-B FIXTURES 96W EACH. |
| | THE OTHER EXTERIOR LIGHT FIXTURES ARE: |
| | 2- D FIXTURES 26W EACH |
| | 1- E FIXTURE 26W. |
| | THE NUMBER OF FIXTURES SHOWN ON EXTERIOR INPUT DATA |
| | REPORT IS OK, ONLY NEED TO UPDATE THE WATTAGE FOR D |
| | FIXTURES. |
| | |
| | OTHER UNITS CONTAIN A DIFFERENT NUMBER OF FIXTURES, |
| | HOWEVER THE SAME COORDINATION NEEDS TO TAKE PLACE. |
| | |
| | ** PLEASE CALL THIS OFFICE TO GO OVER THIS OR IF THERE |
| | ARE ANY QUESTIONS OR COMMENTS IN ANY WAY AS STATED ON |
| | THE PREVIOUS THREE REVIEWS. |
| | |
| | 2) NOTE: PLEASE SEE OWNER INFORMATION ON PERMIT |
| | APPLICATION DOES NOT SHOW THE SAME AS ON OUR SYSTEM. |
| | PLEASE OBTAIN UPDATED DEED, OR PALM BEACH COUNTY |
| | PROPERTY APPRAISER PRINT OUTS SO THE OWNER INFORMATION |
| | CAN BE UPDATED. |
| | *THIS IS NOT FOR ELECTRICAL CODE COMPLIANCE, HOWEVER |
| | THIS IS STILL REQUIRED. |
| | |
| | 3) NOTE: PLEASE KNOW AS A NEW DESIGNER OF RECORD HAS |
| | TAKEN OVER FOR THE ENERGY CALCULATIONS, FS 553.80(2)(B) |
| | DOES NOT APPLY AT THIS TIME. |
| | PLEASE BE SURE TO ADDRESS COMMENT. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |