Plan Review Notes
Plan Review Notes For Permit 06110556
Permit Number 06110556
Review Stop M
Sequence Number 3
Notes
Date Text
2007-04-24 10:01:40*** DENIED ***
 1) ENERGY CALCULATIONS "PREPARED BY" NEED TO BE SIGNED
 AND SEALED BY AN ARCHITECT OR ENGINEER, SEE 2004 FBC
 13-103.1.1.1.
  
 2) ENERGY CALCULATIONS NEED A "MECHANICAL DESIGNER" WHO
 IS A ENGINEER, OR AN ARCHITECT, AIR CONDITIONING
 CONTRACTOR, OR MECHANICAL CONTRACTOR IF APPLICABLE, SEE
 2004 FBC 13-103.1.1.1 AND F.S. 471.003 (H).
  
 *** 2004 FBC 13-103.1.1.1 COMMERCIAL APPLICATIONS.
 COMPLETION OF PROCEDURES DEMONSTRATING COMPLIANCE WITH
 THIS CODE FOR COMMERCIAL BUILDINGS SHALL BE SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER LICENSED TO PRACTICE
 IN THE STATE OF FLORIDA, WITH THE EXCEPTION OF
 BUILDINGS EXCLUDED BY SECTION 481.229, FLORIDA STATUTES
 , OR SECTION 471.003, FLORIDA STATUTES. CALCULATIONS
 FOR BUILDINGS FALLING WITHIN THE EXCEPTION OF SECTION
 471.003, FLORIDA STATUTES , MAY BE PERFORMED BY AIR
 CONDITIONING OR MECHANICAL CONTRACTORS LICENSED IN
 ACCORDANCE WITH CHAPTER 489, FLORIDA STATUTES , OR BY
 STATE OF FLORIDA CERTIFIED COMMERCIAL BUILDING ENERGY
 RATERS.
 DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR
 THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE
 PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT
 INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.