| Plan Review Notes For Permit 06110543 |
| Permit Number |
06110543 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-12-12 15:09:49 | PROVISO: | | | CHILLER INDICATED ON THE PLAN IS FOR EMERGENCY | | | TEMPORARY USE ONLY AND WILL NOT BE INSTALLED | | | PERMENANTLY.CHILL WATER PIPING WILL BE PERMANENT. | | | | | | PER 2004 FMC 1208.1 - HYRDONIC TEST REQUIRED.PLEASE | | | LEAVE ALL JOINTS EXPOSED FOR INSPECTION.TEST WILL | | | CONSIST OF A MINIMUM OF 100 PSI FOR 4 HOURS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|