2006-12-12 15:09:49PROVISO:
 CHILLER INDICATED ON THE PLAN IS FOR EMERGENCY
 TEMPORARY USE ONLY AND WILL NOT BE INSTALLED
 PERMENANTLY.CHILL WATER PIPING WILL BE PERMANENT.
  
 PER 2004 FMC 1208.1 - HYRDONIC TEST REQUIRED.PLEASE
 LEAVE ALL JOINTS EXPOSED FOR INSPECTION.TEST WILL
 CONSIST OF A MINIMUM OF 100 PSI FOR 4 HOURS.
  