Plan Review Notes
Plan Review Notes For Permit 06110536
Permit Number 06110536
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-04 15:56:24DENIED
 REFERENCE: FBC-2004 SEC. 424.2 OR FBCR-2004 SEC.4101
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR SUBMITTALS TO
 REFLECT THE FOLLOWING INFORMATION REQUIRED FOR PLUMBING
 PLAN REVIEW:
  
 1) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 NOTE: PLEASE PROVIDE MANUFACTURE CUT SHEET OR LIST MAKE
 AND MODEL NUMBER OF CLEANING FITTING ON PRINTS.
  
 2) ON SHEET 3 OF 3 THERE IS A HEAT PUMP INDICATED ON
 THE ELECTRICAL SCHEMATIC IS THIS PART OF THE POOL? IF
 NOT PLEASE REMOVE. IF THIS IS PART OF THE POOL PLEASE
 ADD TO PLUMBING SCHEMATIC AND PROVIDE THE FOLLOWING.
 A) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 B) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
 C) FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  