| Plan Review Notes For Permit 06110536 |
| Permit Number |
06110536 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-01 10:44:26 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | PLEASE SUBMIT DETAILS FOR THE PANEL SHOWN ON THE | | | SCHEMATIC, FEEDER AND CONDUIT SIZE AND TYPE, PANEL | | | RATING AND OCP,PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | | IF THIS PANEL IS AN EXISTING POOL PANEL, SIMPLY LABEL | | | IT AS SUCH. | | | IF AN ELECTRIC HEATER IS TO BE INSTALLED AS SHOWN ON | | | THE ELECTRICAL SCHEMATIC,PLEASE SUBMIT CALCULATIONS | | | FOR THE MAIN SERVICE AND SPECIFICATIONS FOR THE | | | HEATER. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|