Plan Review Notes
Plan Review Notes For Permit 06110536
Permit Number 06110536
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-01 10:44:26 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 PLEASE SUBMIT DETAILS FOR THE PANEL SHOWN ON THE
 SCHEMATIC, FEEDER AND CONDUIT SIZE AND TYPE, PANEL
 RATING AND OCP,PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF THIS PANEL IS AN EXISTING POOL PANEL, SIMPLY LABEL
 IT AS SUCH.
 IF AN ELECTRIC HEATER IS TO BE INSTALLED AS SHOWN ON
 THE ELECTRICAL SCHEMATIC,PLEASE SUBMIT CALCULATIONS
 FOR THE MAIN SERVICE AND SPECIFICATIONS FOR THE
 HEATER.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.