| Date |
Text |
| 2007-02-13 16:33:24 | REVISION DENIED |
| | REFERENCE: FBC-2004 FUEL GAS; FLORIDA ADMINISTRATIVE |
| | CODE; CITY OF WEST PALM BEACH GAS PERMIT (REVISION) |
| | REQUIREMENTS; |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PLEASE NOTE THAT THE ORIGINAL CONSTRUCTION |
| | DOCUMENTS ARE SIGNED, DATED AND SEALED BY AN ENGINEER. |
| | PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002, ANY |
| | REVISIONS TO THE CONSTRUCTION DOCUMENTS SHALL BE SIGNED |
| | SEALED AND DATED BY THE ENGINEER OF RECORD EUGENE |
| | PILHUJ, LICENSE NUMBER, P.E. FL. REG. 49832. PLEASE |
| | CORRECT AND RESUBMIT. |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED ON |
| | THE REVISION, PLEASE CORRECT AND RESUBMIT. |
| | |
| | 3. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: NOT ALL PIPING MATERIALS OR SIZES ARE INDICATED |
| | ON THE RESUBMITTAL AND PLEASE NOTE THAT THE REVISED GAS |
| | DRAWING IS SIZED WRONG . PLEASE REFERENCE THE ATTACHED |
| | FBC-2004 FUEL GAS SIZING TABLES FOR THE REVISION |
| | RESUBMITTAL. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THE ADDED LONGEST LENGTH OF THE INDICATED PIPE |
| | COMES TO 60'-11", BUT NOT ALL CORRESPONDING LENGTHS ARE |
| | INDICATED ON ALL CUT SECTIONS OF PIPEON THE REVISION. |
| | PLEASE CORRECT AND INDICATE THE LONGEST LENGTH ON THE |
| | RESUBMITTED REVISION. |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| | ON THE RESUBMITTED REVISION |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | NOTE: THE DELIVERY PRESSURE IS NOT INDICATED ON THE |
| | REVISION, PLEASE CORRECT THIS ON THE RESUBMITTED |
| | REVISION. |
| | |
| | **********IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |