| Plan Review Notes For Permit 06110514 |
| Permit Number |
06110514 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-08-06 11:42:40 | THIRD REVIEW | | | 2004 FBC | | | RENOVATE AND INCREASE FIRST FLOOR GARAGE AREA AND ADD | | | SECOND FLOOR LIVING SPACE TO EXISTING DETACHED GARAGE | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SHOP DRAWINGS FOR THE SPIRAL STAIR WILL BE REQUIRED | | | TO BE SUBMITTED FOR PLAN REVIEW PRIOR TO INSTALLATION. | | | | | | 3) ROOF SECTIONS 3, 10 AND 11 ON S2 INCORRECTLY SPECIFY | | | THE RAFTERS AS FLOOR JOISTS. PLEASE CORRECT. SEE | | | COMMENT #14 FROM LAST REVIEW. | | | | | | 4) THE PRODUCT APPROVALS FOR THE SIMPSON CONNECTORS | | | SUBMITTED ARE NOT APPLICABLE. THERE ARE NO SIMPSON | | | CONNECTORS SPECIFIED ON THE PLANS. SEE COMMENT # 17 | | | FROM LAST REVIEW. PLEASE REMOVE THESE FROM THE | | | SUBMITTALS. | | | | | | 5) THE RAS 117 CALCULATIONS FOR THE SEALOFLEX | | | WATERPROOFING SYSTEM IS INCORRECT. THE RESULTS OF THE | | | CALCULATIONS HAVE THE FASTENERS ARE SPACED FARTHER | | | APART THAN SPECIFIED IN THE NOA FOR THE DESIGN | | | PRESSURE. THE SPACING SHOULD BE CLOSER FOR ENHANCED | | | FASTENING. PLEASE CORRECT. | | | | | | 6) SUBMIT THE OLD PLAN SHEETS WITH THE COUNTY IMPACT | | | FEE STAMP OR HAVE THE NEW ONES STAMPED BY THE COUNTY. | | | | | | 7) HAVE THE NEW PLANS REVIEWED AND APPROVED BY THE CITY | | | OF WPB HISTORIC PLANNING DEPARTMENT. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | |
|