| 2006-12-05 18:23:26 | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} 240.24(B) OCCUPANCY. EACH OCCUPANT SHALL HAVE READY |
| | ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE |
| | CONDUCTORS SUPPLYING THAT OCCUPANCY. |
| | |
| | 2} THE PANEL AT THE GARAGE MUST BE GROUNDED PER 250.32, |
| | SIZED PER 250.66. |
| | |
| | 3} THE PANEL AT THE GARAGE MUST CONTAIN A MAIN |
| | DISCONNECT PER 230.70, LOCATED PER 225.32, OR A |
| | DISCONNECT MUST BE INSTALLED. |
| | |
| | 4} VERIFY THAT THE METER ON THE RISER IS A CURRENT |
| | TRANSFORMER TYPE METER AS THIS IS UNUSUAL FOR A |
| | RESIDENTIAL SERVICE.THE RISER MUST BE CORRECT OR WILL |
| | HAVE TO BE RESUBMITTED LATER PROBABLY CAUSING A DELAY |
| | IN THE JOB PROGRESS. |
| | |
| | 5} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| | ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| | FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| | |
| | 6} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 7} THE ENGINEER OF RECORD SHALL INDICATE THE |
| | CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER |
| | INFORMATION REQUIRED BY 61G15-23.002FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | WILLIAM R. TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |