| Plan Review Notes For Permit 06110506 |
| Permit Number |
06110506 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-02-01 08:26:35 | BUILDING REVIEW THIRDCHECKLIST: | | | 1- ON PREVIOUS CHECKLIST CONTRACTOR WAS ASKED TO | | | PROVIDE COMPLETE INSTALLATION SCHEDULE.SAMPLE OF | | | INSTALLATION SCHEDULEWAS PROVIDED. CONTRACTOR DID NOT | | | PROVIDE ANY TYPE OF INSTALLATION SCHEDULE.PROVIDE | | | COMPLETE INSTALLATION SCHEDULE. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | THE FOLLOWING INFORMATION IS REQUIRED TO PERFORM PLAN | | | REVIEW: OPENING DESIGN PRESSURES, EDGE DISTANCE, PANEL | | | SPAN,SPECIFIC MOUNTING CONDITIONS, CONNECTION TYPE, | | | ANCHOR TYPE AND SPACING AND SPECIFIC STRUCTURE TO BE | | | ATTACHED TO (CONCRETE, CONCRETE BLOCK OR WOOD). | | | | | | ***NOTE: ENGINEERED DRAWINGS WERE CIRCLED, BUT THIS | | | DOESN'T PROVIDE ALL REQUIRED INFORMATION TO VERIFY | | | COMPLIANCE WITH PRODUCT APPROVAL AND PROPOSED | | | INSTALLATION. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|