| Plan Review Notes For Permit 06110506 |
| Permit Number |
06110506 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-17 08:18:28 | BUILDING REVIEW CHECKLIST: | | | 1- PROVIDE APPROVED PRODUCT APPROVAL FOR ACCORDION | | | SHUTTERS AS REQUIRED BY DCA RULE 9B-72. INFORMATION | | | SUBMITTED IS NOT AN APPROVED PRODUCT APPROVAL. | | | | | | 2- PROVIDE COMPLETE INSTALLATION SCHEDULE. YOU MAY USE | | | ATTACHED SAMPLE THAT CONTAINS ALL REQUIRED INFORMATION | | | FOR EACH OPENING TO VERIFY COMPLIANCE WITH PRODUCT | | | APPROVAL PROPOSED INSTALLATION.COMPLETE INFORMATION | | | FOR PLAN REVIEW INCLUDES: DESIGN PRESSURES, EDGE | | | DISTANCE, PANEL SPAN, MOUNTING CONDITIONS, ANCHOR TYPE | | | AND STRUCTURE TO BE ATTACHED TO (CONCRETE, CONCRETE | | | BLOCK OR WOOD). SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|