| 2007-01-23 13:14:58 | BUILDING REVIEW SECOND CHECKLIST: | | | 1- ON PREVIOUS CHECKLIST CONTRACTOR WASASKED TO | | | PROVIDE THE STORM SHUTTERS PRODUCT APPROVAL AS REQUIRED | | | BY DCA RULE 9B-72. THIS TIME CONTRACTOR SUBMITTED | | | FLORIDA PRODUCT APPROVALFL7279, BUT THERE WERE NOT | | | DRAWINGS SUBMITTED. UNABLE TO PERFORM PLAN REVIEW IF | | | THERE ARE NOT DRAWINGS TO REVIEW. | | | | | | 2- ON PREVIOUS CHECKLIST CONTRACTOR WAS ASKED TO | | | PROVIDE COMPLETE INSTALLATION SCHEDULE.SAMPLE OF | | | INSTALLATION SCHEDULEWAS PROVIDED. CONTRACTOR DID NOT | | | PROVIDE ANY TYPE OF INSTALLATION SCHEDULE.PROVIDE | | | COMPLETE INSTALLATION SCHEDULE. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | THE FOLLOWING INFORMATION IS REQUIRED TO PERFORM PLAN | | | REVIEW: OPENING DESIGN PRESSURES, EDGE DISTANCE, PANEL | | | SPAN,SPECIFIC MOUNTING CONDITIONS, CONNECTION TYPE, | | | ANCHOR TYPE AND SPACING AND SPECIFIC STRUCTURE TO BE | | | ATTACHED TO (CONCRETE, CONCRETE BLOCK OR WOOD). | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|