2007-01-23 13:14:58BUILDING REVIEW SECOND CHECKLIST:
 1- ON PREVIOUS CHECKLIST CONTRACTOR WASASKED TO
 PROVIDE THE STORM SHUTTERS PRODUCT APPROVAL AS REQUIRED
 BY DCA RULE 9B-72. THIS TIME CONTRACTOR SUBMITTED
 FLORIDA PRODUCT APPROVALFL7279, BUT THERE WERE NOT
 DRAWINGS SUBMITTED. UNABLE TO PERFORM PLAN REVIEW IF
 THERE ARE NOT DRAWINGS TO REVIEW.
  
 2- ON PREVIOUS CHECKLIST CONTRACTOR WAS ASKED TO
 PROVIDE COMPLETE INSTALLATION SCHEDULE.SAMPLE OF
 INSTALLATION SCHEDULEWAS PROVIDED. CONTRACTOR DID NOT
 PROVIDE ANY TYPE OF INSTALLATION SCHEDULE.PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 THE FOLLOWING INFORMATION IS REQUIRED TO PERFORM PLAN
 REVIEW: OPENING DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN,SPECIFIC MOUNTING CONDITIONS, CONNECTION TYPE,
 ANCHOR TYPE AND SPACING AND SPECIFIC STRUCTURE TO BE
 ATTACHED TO (CONCRETE, CONCRETE BLOCK OR WOOD).
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER