| 2006-11-28 16:01:42 | *** DENIED *** |
| | 1) DUE TO THE 1000 GAL. FUEL TANK THE PLANS NEED TO BE |
| | APPROVED BY THE FL. DEPT. OF ENVIRONMENTAL PROTECTION |
| | (2300 N. JOG RD. W.P.B. (561) 233-2400) BEFORE APPLYING |
| | FOR PERMIT. |
| | |
| | 2) INFORMATIONAL ONLY. PER 2004 FBC, FUEL GAS - |
| | POWERED |
| | EQUIPMENT - PERMANENTLY INSTALLED |
| | EQUIPMENT POWERED BY INTERNAL COMBUSTION |
| | ENGINES SHALL BE INSTALLED IN ACCORDANCE |
| | WITH MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS AND NFPA 37. |
| | |
| | NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION |
| | ENGINES & GAS TURBINES: |
| | 4.1.4ENGINES (GENERATORS) LOCATED |
| | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM |
| | OPENINGS IN WALLS & AT LEAST 5 FT FROM |
| | STRUCTURES HAVING COMBUSTIBLE WALLS.A |
| | MINIMUM CLEARANCE IS NOT REQUIRED WHEN |
| | (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE |
| | RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS |
| | CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS |
| | BEEN DEMONSTRATED THAT A FIRE WITHIN THE |
| | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS OUTSIDE THE ENCLOSURE. |
| | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS |
| | SHOULD NOT TERMINATE UNDER STRUCTURES OR |
| | WHERE THE EXHAUST MIGHT BE DRAWN INTO |
| | THE VENTILATION INTAKES. |
| | |
| | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE |
| | MENTIONED CLEARANCES TO THE ADJACENT |
| | PROPERTY STRUCTURES, I.E. FENCE, |
| | BUILDING, WINDOWS, DOORS, OR OPENINGS. |
| | |
| | FUEL STORAGE TANK MUST BE A MINIMUM DISTANCE OF 5 FEET |
| | FROM BUILDING, SEE NFPA 30 CH. 4, 4.3.2.1.1. |
| | |
| | FOLLOW MANUFACTURER'S RECOMMENDED |
| | CLEARANCES AROUND EQUIPMENT FOR |
| | SERVICING,AND PROVIDE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS AT THE JOBSITE |
| | FOR THE FIELD INSPECTOR. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |