| Plan Review Notes For Permit 06110497 |
| Permit Number |
06110497 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-20 18:53:02 | BUILDING PLAN REVIEW | | | PERMIT:06110497 | | | ADD:10130 NORTHLAKE BLVD. #651 | | | CONT:POWER SECURE INC. | | | TEL: (866)347-5455 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW : 1ST | | | ACTION: DENIED | | | | | | 1) 2004 FL. BLD CODE 1603.1.4 THE | | | FOLLOWING INFORMATION RELATED TO WIND | | | SHALL BE SHOWN ON THE CONSTRUCTION | | | DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | | | | 2)SHOW CLEARLY ON THE DRAWINGS THE DISTANCE THE | | | GENERATOR WILL BE INSTALLED FROM THE BUILDING. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | | | | | | | | | | | | | |
|