Plan Review Notes
Plan Review Notes For Permit 06110482
Permit Number 06110482
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-11-30 13:00:30*****UNSAT*****
  
  
  
 1.THE PERMIT APPLICATION AND THE CITY'S COMPUTER
 ENTRY SYSTEM STATES THAT THE ADDRESS IS 309 CLEMATIS
 STREET, HOWEVER THE ADDRESS REFLECTED ON THE SUBMITTED
 PLANS IS 311 CLEMATIS STREET.THE ADDRESS ON THE
 PERMIT AND PLANS MUST BE THE SAME.FOR ADDRESSING
 MATTERS, CONTACT LILI URSA AT 561-822-1239.
  
 2.APRESSURE TEST WILL BE REQUIRED SINCE THE
 MODIFICATION AFFECTS MORE THAN 20 HEADS.HOWEVER, IF
 THE MODIFICATION CANNOT BE ISOLATED AS PER NFPA
 16.2.1.6, A LETTER FROM YOUR COMPANY STATING SUCH AT
 THE SAID LOCATION SHALL BE PROVIDED TO THE FIRE
 PREVENTION BUREAUPRIOR TO OR AT THE TIME OF
 INSPECTION.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722