2007-02-10 15:05:10BUILDING REVIEW SECOND CHECKLIST:
 1- SEE STORM SHUTTERS DRAWINGS AND INDICATE SPECIFIC
 MOUNTING CONDITIONS, CORRECT ANCHOR TYPE FOR WOOD
 INSTALLATION AND ANCHOR SPACING.
  
 2- SHUTTER SPAN IS THE LONG DIMENSION OF THE PANEL, NOT
 THE WIDTH OF THE PANEL. REVISE AS REQUIRED.
  
 3- CLARIFY IF THE EDGE DISTANCE IS REALLY 6". HOW IS
 THE OPENING FRAMED TO ALLOW 6" EDGE DISTANCE ON TOP AND
 BOTTOM OF OPENING.
  