| 2006-11-29 14:55:01 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW . |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 2} INDICATE COMPLIANCE WITH250.50 GROUNDING ELECTRODE |
| | SYSTEM. |
| | IF AVAILABLE ON THE PREMISES AT EACH BUILDING OR |
| | STRUCTURE SERVED, EACH ITEM IN 250.52(A)(1) THROUGH |
| | (A)(6) SHALL BE BONDED TOGETHER TO FORM THE GROUNDING |
| | ELECTRODE SYSTEM. WHERE NONE OF THESE ELECTRODES ARE |
| | AVAILABLE, ONE OR MORE OF THE ELECTRODES SPECIFIED IN |
| | 250.52(A)(4) THROUGH (A)(7) SHALL BE INSTALLED AND |
| | USED. INDICATE ALL OTHER ITEMS INCLUDED IN THIS SYSTEM |
| | ALONG WITH THE GROUND RODS ON THE RISER. |
| | |
| | 3} THE GROUNDED CONDUCTOR (NEUTRAL) MUST COMPLY WITH |
| | 250.24(B) (1):ROUTING AND SIZING. "THIS CONDUCTOR |
| | SHALL BE ROUTED WITH THE PHASE CONDUCTORS AND SHALL NOT |
| | BE SMALLER THAN THE REQUIRED GROUNDING ELECTRODE |
| | CONDUCTOR SPECIFIED IN TABLE 250.66---". THEREFORE A |
| | MINIMUM OF 2/0 COPPER IS REQUIRED. INDICATE SAME ON THE |
| | RISER FROM THE TRANSFORMER TO THE 600 AMP MLO MAIN |
| | PANEL. |
| | |
| | 4} ACKNOWLEDGE 230.2(E), IDENTIFICATION IS REQUIRED-" |
| | WHERE A BUILDING OR STRUCTURE IS SUPPLIED BY MORE THAN |
| | ONE SERVICE, OR ANY COMBINATION OF BRANCH CIRCUITS, |
| | FEEDERS, AND SERVICES, A PERMANENT PLAQUE OR DIRECTORY |
| | SHALL BE INSTALLED AT EACH SERVICE DISCONNECT LOCATION |
| | DENOTING ALL OTHER SERVICES, FEEDERS, AND BRANCH |
| | CIRCUITS SUPPLYING THAT BUILDING OR STRUCTURE AND THE |
| | AREA SERVED BY EACH". A NOTE ON THE PLAN WILL SUFFICE. |
| | THE INTENT OF THIS COMMENT IS TO MAKE THE CONTRACTOR |
| | AWARE OF THIS REQUIREMENT SO AS TO AVOID FINDING OUT |
| | AND DELAYING THE FINAL INSPECTION. |
| | |
| | 5} NOTE #3 IN THE ELECTRICAL NOTES INCORRECTLY |
| | REFERENCES THE "LATEST EDITION" OF THE NEC. CURRENTLY |
| | THE 2002 NEC IS IN EFFECT. THE LATEST EDITION, 2005, |
| | WILL NOT BE IMPLEMENTED IN FLORIDA UNTILL DECEMBER 8, |
| | 2006. PLEASE CORRECT THE NOTE TO REFERENCE THE CORRECT |
| | CODE CYCLE. |
| | |
| | 6} THE SPRAY BOOTH"HOOK UP" INDICATED ON THE |
| | APPLICATION WILL PREVENT THE ISSUE OF THIS PERMIT |
| | UNTILL THAT APPLICATION IS PERMITTED. ALSO THE BOOTHS |
| | LOCATION IS NOT ON THE PLAN, AND THE PANEL FEEDING THAT |
| | BOOTH PRESUMED TO BE #12, IS MISMARKED AS "GEN". PLEASE |
| | SHOW ALL EQUIPMENT RELEVANT TO THIS APPLICATION. |
| | |
| | 7} INDICATE CLASS AND DIVISION OF THE BOOTH WIRING. |
| | SHOW COMPLIANCE WITH ARTICLE 516 AND CHAPTER 6, NFPA |
| | 33. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |