Notes
Date Text
2006-11-29 14:55:01 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW .
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 2} INDICATE COMPLIANCE WITH250.50 GROUNDING ELECTRODE
 SYSTEM.
 IF AVAILABLE ON THE PREMISES AT EACH BUILDING OR
 STRUCTURE SERVED, EACH ITEM IN 250.52(A)(1) THROUGH
 (A)(6) SHALL BE BONDED TOGETHER TO FORM THE GROUNDING
 ELECTRODE SYSTEM. WHERE NONE OF THESE ELECTRODES ARE
 AVAILABLE, ONE OR MORE OF THE ELECTRODES SPECIFIED IN
 250.52(A)(4) THROUGH (A)(7) SHALL BE INSTALLED AND
 USED. INDICATE ALL OTHER ITEMS INCLUDED IN THIS SYSTEM
 ALONG WITH THE GROUND RODS ON THE RISER.
  
 3} THE GROUNDED CONDUCTOR (NEUTRAL) MUST COMPLY WITH
 250.24(B) (1):ROUTING AND SIZING. "THIS CONDUCTOR
 SHALL BE ROUTED WITH THE PHASE CONDUCTORS AND SHALL NOT
 BE SMALLER THAN THE REQUIRED GROUNDING ELECTRODE
 CONDUCTOR SPECIFIED IN TABLE 250.66---". THEREFORE A
 MINIMUM OF 2/0 COPPER IS REQUIRED. INDICATE SAME ON THE
 RISER FROM THE TRANSFORMER TO THE 600 AMP MLO MAIN
 PANEL.
  
 4} ACKNOWLEDGE 230.2(E), IDENTIFICATION IS REQUIRED-"
 WHERE A BUILDING OR STRUCTURE IS SUPPLIED BY MORE THAN
 ONE SERVICE, OR ANY COMBINATION OF BRANCH CIRCUITS,
 FEEDERS, AND SERVICES, A PERMANENT PLAQUE OR DIRECTORY
 SHALL BE INSTALLED AT EACH SERVICE DISCONNECT LOCATION
 DENOTING ALL OTHER SERVICES, FEEDERS, AND BRANCH
 CIRCUITS SUPPLYING THAT BUILDING OR STRUCTURE AND THE
 AREA SERVED BY EACH". A NOTE ON THE PLAN WILL SUFFICE.
 THE INTENT OF THIS COMMENT IS TO MAKE THE CONTRACTOR
 AWARE OF THIS REQUIREMENT SO AS TO AVOID FINDING OUT
 AND DELAYING THE FINAL INSPECTION.
  
 5} NOTE #3 IN THE ELECTRICAL NOTES INCORRECTLY
 REFERENCES THE "LATEST EDITION" OF THE NEC. CURRENTLY
 THE 2002 NEC IS IN EFFECT. THE LATEST EDITION, 2005,
 WILL NOT BE IMPLEMENTED IN FLORIDA UNTILL DECEMBER 8,
 2006. PLEASE CORRECT THE NOTE TO REFERENCE THE CORRECT
 CODE CYCLE.
  
 6} THE SPRAY BOOTH"HOOK UP" INDICATED ON THE
 APPLICATION WILL PREVENT THE ISSUE OF THIS PERMIT
 UNTILL THAT APPLICATION IS PERMITTED. ALSO THE BOOTHS
 LOCATION IS NOT ON THE PLAN, AND THE PANEL FEEDING THAT
 BOOTH PRESUMED TO BE #12, IS MISMARKED AS "GEN". PLEASE
 SHOW ALL EQUIPMENT RELEVANT TO THIS APPLICATION.
  
 7} INDICATE CLASS AND DIVISION OF THE BOOTH WIRING.
 SHOW COMPLIANCE WITH ARTICLE 516 AND CHAPTER 6, NFPA
 33.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.