2007-01-02 09:01:48DENIED;
 1.SANITARY RISER DIAGRAM PIPE SIZING NOT TO CODE, WET
 VENT PIPE FOR MASTER BATH W/C TO BE 3" SEE TABLE
 909.3.
 2. AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3" SEE
 SECTION 406.3, AND CLEANOUT TO BE AT 48" AFF.
 3. 2 TUBS AND ONE SHOWER ON FLOOR PLAN CHANGE RISER
 DIAGRAM TO REFECT SAME.
 ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;