Plan Review Notes
Plan Review Notes For Permit 06110438
Permit Number 06110438
Review Stop M
Sequence Number 1
Notes
Date Text
2007-01-02 10:55:24*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.2.
  
 2) PLEASE SUBMIT MANUAL J CALCULATIONS, PER 2004 FBC/R
 M1401.3.
  
 3) SEE MECHANICAL PLANS PAGE M-1 EQUIPMENT SCHEDULE,
 AIR HANDLER AND CONDENSER UNIT MODEL NUMBERS DID NOT
 MATCH UP IN THE ARI UNITARY DIRECTORY, PLEASE CHECK AND
 CORRECT.
  
 4) SEE MECHANICAL PLANS PAGE M-1 EQUIPMENT SCHEDULE A/C
 SYSTEM IS LISTED AS 119 SEER, PLEASE CORRECT.
  
 5) PLEASE SHOW THE SIZE OF THE SUPPLY AIR AND RETURN
 AIR MAIN TRUNK LINE DUCTS TO EACH AIR HANDLER UNIT ON
 MECHANICAL PLANS.
  
 6) PLEASE SHOW LOCATION OF ACCESS HATCHES TO ALL AIR
 HANDLER UNITS ON MECHANICAL PLANS, SEE 2004 FBC/R
 M1305.1.3.
  