| Plan Review Notes For Permit 06110438 |
| Permit Number |
06110438 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-02 10:55:24 | *** DENIED *** | | | 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-101.2.2. | | | | | | 2) PLEASE SUBMIT MANUAL J CALCULATIONS, PER 2004 FBC/R | | | M1401.3. | | | | | | 3) SEE MECHANICAL PLANS PAGE M-1 EQUIPMENT SCHEDULE, | | | AIR HANDLER AND CONDENSER UNIT MODEL NUMBERS DID NOT | | | MATCH UP IN THE ARI UNITARY DIRECTORY, PLEASE CHECK AND | | | CORRECT. | | | | | | 4) SEE MECHANICAL PLANS PAGE M-1 EQUIPMENT SCHEDULE A/C | | | SYSTEM IS LISTED AS 119 SEER, PLEASE CORRECT. | | | | | | 5) PLEASE SHOW THE SIZE OF THE SUPPLY AIR AND RETURN | | | AIR MAIN TRUNK LINE DUCTS TO EACH AIR HANDLER UNIT ON | | | MECHANICAL PLANS. | | | | | | 6) PLEASE SHOW LOCATION OF ACCESS HATCHES TO ALL AIR | | | HANDLER UNITS ON MECHANICAL PLANS, SEE 2004 FBC/R | | | M1305.1.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|