| Plan Review Notes For Permit 06110438 |
| Permit Number |
06110438 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-22 10:30:19 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 2} THE GROUND DETAIL SHEET E-2, INCORRECTLY LISTS A #6 | | | CU CONDUCTOR BEING RAN TO THE FOOTER STEEL. THE MINIMUM | | | SIZE PER 250.66(B) IS #4 CU. | | | | | | 3} PANEL "A", CIRCUIT 2-4, YHE OCP IS INCORRECT FOR THE | | | LOAD, 15 AMP FOR 5KW.240.4. | | | | | | 4} THE SMALL APPLIANCE CIRCUITS 22&24, PANEL "A" MUST | | | HAVE A 20 AMP BRAEKER PER 210.11(C)(1). | | | | | | 5} THE HEATING LOADS ON THE PANEL SCHEDULES DO NOT | | | MATCH THE ONES IN THE CALCULATION, OR THE DEMAND @ 65%. | | | PLEASE CORRELATE. | | | | | | 6} 210.8(A)(6) REQUIRES ALL COUNTERTOP RECEPTACLES | | | (KITCHEN) BE GFCI PROTECTED.SEE PENINSULA. | | | | | | 7} 210.8(A)(2) REQUUIRES GFCI PROTECTION IN GARAGES. | | | SEE SOUTH WALL, THREE RECEPTACLES. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|