2006-12-22 10:30:19 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} THE GROUND DETAIL SHEET E-2, INCORRECTLY LISTS A #6
 CU CONDUCTOR BEING RAN TO THE FOOTER STEEL. THE MINIMUM
 SIZE PER 250.66(B) IS #4 CU.
  
 3} PANEL "A", CIRCUIT 2-4, YHE OCP IS INCORRECT FOR THE
 LOAD, 15 AMP FOR 5KW.240.4.
  
 4} THE SMALL APPLIANCE CIRCUITS 22&24, PANEL "A" MUST
 HAVE A 20 AMP BRAEKER PER 210.11(C)(1).
  
 5} THE HEATING LOADS ON THE PANEL SCHEDULES DO NOT
 MATCH THE ONES IN THE CALCULATION, OR THE DEMAND @ 65%.
 PLEASE CORRELATE.
  
 6} 210.8(A)(6) REQUIRES ALL COUNTERTOP RECEPTACLES
 (KITCHEN) BE GFCI PROTECTED.SEE PENINSULA.
  
 7} 210.8(A)(2) REQUUIRES GFCI PROTECTION IN GARAGES.
 SEE SOUTH WALL, THREE RECEPTACLES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.