| 2007-03-27 13:10:56 | DENIED BY BUILDING (2ND REVIEW) |
| | |
| | THE FOLLOWING ITEMS FROM THE FIRST REVIEW WERE NOT |
| | ADDRESSED. |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2)SPECIFY THE SIZE OF THE REMAINING WINDOW IN THE |
| | BEDROOM ADJACENT TO THE NEW ADDITION. SEE R 310 FOR |
| | EMERGENCY EGRESS REQUIREMENTS. |
| | |
| | 3)THE NEW BATHROOM DOOR IS REQUIRED TO HAVE A 29" |
| | CLEAR OPENING. SEE R 322. |
| | |
| | 4) SUBMIT SIGNED AND SEALED TRUSS DRAWINGS REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD AS REQUIRED BY |
| | R802.1.6.1. GIVE TO BUILDING INSPECTOR IN THE FIELD. |
| | |
| | 5) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | REQUIREMENTS OF R401.3. |
| | |
| | 6) THE TRUSS CONNECTION FOR THE SIMPSON HTSM16 REQUIRES |
| | (8) 10D NAILS FOR THE STATED UPLIFT VALUE PER THE |
| | SIMPSON CATALOG. PLEASE REVISE. |
| | |
| | 7) THE CORNERS OF HIP ROOFS ARE ALSO ZONE 3. PLEASE |
| | CORRECT THE ROOF ZONE DIAGRAM ON SHEET 11. SEE FIGURE |
| | 803.2.3.1 AND FBC FIGURE 1609.6.2.2. |
| | |
| | 8) SPECIFY THE ROOF VENTILATION AS REQUIRED BY R 806. |
| | |
| | 9) SPECIFY THE SIZE AND LOCATION OF THE ATTIC ACCESS |
| | REQUIRED BY R 807. |
| | |
| | 10) SAFETY GLAZING IS REQUIRED IN BATHROOM WINDOW PER R |
| | 308.4 IF BOTTOM OF WINDOW IS LESS THAN 60" ABOVE |
| | FLOOR. |
| | |
| | 11) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW |
| | MULLIONS. |
| | |
| | 12) SUBMIT FLORIDA PRODUCT APPROVAL COVERSHEETS FOR THE |
| | 2004 CODE EDITION. MOST OF THE ONES SUBMITTED ARE FOR |
| | 2001 CODE. |
| | |
| | 13) SEVERAL OF THE MIAMI-DADE NOAS THAT WERE SUBMITTED |
| | ARE EXPIRED. PLEASE REVIEW THE PRODUCT APPROVALS AND |
| | SUBMIT CURRENT INFORMATION. |
| | |
| | 14) ONLY TWO COMPLETE SETS OF PLANS AND SUBMITTALS ARE |
| | REQUIRED. |
| | |
| | PLEASE SUBMIT A TRANSMITTAL LETTER WITH THE RESUBMITTAL |
| | INDICATING HOW THE COMMENTS HAVE BEEN ADDRESSED. |
| | |
| | NEW ITEMS : |
| | |
| | 15) THE REAR ELEVATION ON SHEET 4 DOES NOT SHOW THE |
| | EXTERIOR DOOR TO THE BATHROOM. |
| | |
| | 16) ON SHEET 9, SIMPSON META 14 CONNECTORS ARE |
| | SPECIFIED AT AN EXISTING WALL OF THE NEW LAUNDRY ROOM. |
| | PLEASE SPECIFY AN APPROPRIATE CONNECTOR. SEE RED MARKS |
| | ON PLANS. |
| | |
| | ROBERT MCDOUGAL |