| Notes |
| Date |
Text |
| 2006-11-30 16:29:55 | UNSAT | | | REFERENCE: FBC-2004 PLUMBING,FBC-2004 CHAPTER 1 AND | | | STATE STATUTES | | | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING | | | PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. PER STATE STATUTES CHAPTER 489, PART 1 AN OWNER | | | BUILDER CAN NOT DO THE WORK ON THEIR CONDO. | | | | | | 2. PER FBC-2004, CHAPTER 1, SECTION 106.3.5.1.3: PLEASE | | | SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM | | | INDICATING ALL WASTE, VENTS, TRAPS WITH SIZES, AND | | | CLEANOUT LOCATIONS OF THE CHANGES IN THE KITCHEN. | | | | | | 3. PER FBC-2004, CHAPTER 1, SECTION 106.3.5.1.3: PLEASE | | | SUBMIT A WATER ISOMETRIC RISER DIAGRAM INDICATING | | | SIZES, SHUT OFF VALVES, AND WATER HAMMER-ARRESTOR | | | LOCATIONS IN RELATION TO QUICK-CLOSING VALVES. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | | | | | | | |
|